Parameter details<br />

Range of Current Trip point<br />

5 — 120% of nominal input<br />

Range of Rated Voltage Trip point 80 — 120% of nominal input<br />

Range of Time-Current Characteristic Curves (Time Curve)<br />

1 St<strong>and</strong>ard Inverse<br />

2 Very Inverse<br />

3 Extremely Inverse<br />

Time Dial Setting Range 0.1 to 9.9<br />

Time Dial Setting Resolution 0.1<br />

Resolution of curve timebase<br />

100 milliseconds<br />

Accuracy of timing (relative to the ± 5% of ideal + 2 loop times<br />

characteristics described below)<br />

Maximum Input current for which 25 Amps for 5 Amp nominal unit<br />

Time-Current characteristics are valid 5 Amps for 1 Amp nominal unit<br />

TYPE 51G — TIME OVER CURRENT NEUTRAL GROUND FAULT CHECK<br />

Brief details<br />

This trip has different implementations on models SPR-013 <strong>and</strong> SPR-014, as follows:<br />

SPR-014 (3 phase 4-wire systems with neutral CT): The fault current is calculated as the<br />

difference between the vector sum of the three phase current inputs <strong>and</strong> the neutral current<br />

input.<br />

SPR-013 (3 phase 3-wire systems): The fault current is the vector sum of the three phase current<br />

inputs only. Do not connect any signal to the Neutral current input terminals.<br />

IMPORTANT: Ground fault current is not directly measured. This parameter is derived<br />

by calculation. This unit has not been tested to UL 1053. The trip function is intended<br />

for monitoring purposes only.<br />

Parameters<br />

You must specify the following parameters for operation of the neutral ground fault relay:<br />

●<br />

The maximum permitted value of the RMS of the vector sum of phase current inputs<br />

<strong>and</strong> the neutral current input from the “generator”.<br />

●<br />

The “Time Dial Setting”.<br />

63