Parameter details<br />
Range of Current Trip point<br />
5 — 120% of nominal input<br />
Range of Rated Voltage Trip point 80 — 120% of nominal input<br />
Range of Time-Current Characteristic Curves (Time Curve)<br />
1 St<strong>and</strong>ard Inverse<br />
2 Very Inverse<br />
3 Extremely Inverse<br />
Time Dial Setting Range 0.1 to 9.9<br />
Time Dial Setting Resolution 0.1<br />
Resolution of curve timebase<br />
100 milliseconds<br />
Accuracy of timing (relative to the ± 5% of ideal + 2 loop times<br />
characteristics described below)<br />
Maximum Input current for which 25 Amps for 5 Amp nominal unit<br />
Time-Current characteristics are valid 5 Amps for 1 Amp nominal unit<br />
TYPE 51G — TIME OVER CURRENT NEUTRAL GROUND FAULT CHECK<br />
Brief details<br />
This trip has different implementations on models SPR-013 <strong>and</strong> SPR-014, as follows:<br />
SPR-014 (3 phase 4-wire systems with neutral CT): The fault current is calculated as the<br />
difference between the vector sum of the three phase current inputs <strong>and</strong> the neutral current<br />
input.<br />
SPR-013 (3 phase 3-wire systems): The fault current is the vector sum of the three phase current<br />
inputs only. Do not connect any signal to the Neutral current input terminals.<br />
IMPORTANT: Ground fault current is not directly measured. This parameter is derived<br />
by calculation. This unit has not been tested to UL 1053. The trip function is intended<br />
for monitoring purposes only.<br />
Parameters<br />
You must specify the following parameters for operation of the neutral ground fault relay:<br />
●<br />
The maximum permitted value of the RMS of the vector sum of phase current inputs<br />
<strong>and</strong> the neutral current input from the “generator”.<br />
●<br />
The “Time Dial Setting”.<br />
63