Parameter details<br />
Range of Current Trip point (TripPoint)<br />
Range of Hysteresis (Diff)<br />
Range of Time Delay (TimeDelay)<br />
Accuracy of Trip Point<br />
5 — 120% of nominal input<br />
1 — 15% of nominal input<br />
0 to 30 seconds<br />
±5% of nominal input<br />
TYPE 32O — DIRECTIONAL (FORWARD) OVER POWER<br />
Brief details<br />
The relay will operate (trip) when the power level out of the “generator” on any phase exceeds<br />
the selected value for the duration of the time delay. The relay will return to the “not tripped”<br />
condition (provided that latched operation has not been selected) when the power level from the<br />
“generator” on all phases falls below the selected trip point by at least the hysteresis value. The<br />
time delay is not used on the transition to the “not tripped” condition.<br />
The function is intended to detect conditions such as generator overload.<br />
Parameters<br />
The following parameters must be specified for the operation of the directional power (forward<br />
or export) relay::<br />
●<br />
(SPR-014) The maximum permitted power on any phase out of the “generator”.<br />
• (SPR-013) The maximum permitted system power out of the “generator”.<br />
●<br />
The time for which the directional power conditions must be true.<br />
●<br />
The power level below the previously defined maximum that all phases from the<br />
“generator” must exceed to return operation to the not tripped condition following a<br />
trip. (Hysteresis)<br />
Parameter details<br />
Range of Directional Power trip (TripPoint) 3 — 120% of nominal power per phase (line)<br />
Range of Hysteresis (Diff)<br />
1 — 15% of nominal power per phase<br />
Range of Time Delay (TimeDelay) 0 to 30 seconds<br />