Parameter details<br />

Range of Current Trip point (TripPoint)<br />

Range of Hysteresis (Diff)<br />

Range of Time Delay (TimeDelay)<br />

Accuracy of Trip Point<br />

5 — 120% of nominal input<br />

1 — 15% of nominal input<br />

0 to 30 seconds<br />

±5% of nominal input<br />

TYPE 32O — DIRECTIONAL (FORWARD) OVER POWER<br />

Brief details<br />

The relay will operate (trip) when the power level out of the “generator” on any phase exceeds<br />

the selected value for the duration of the time delay. The relay will return to the “not tripped”<br />

condition (provided that latched operation has not been selected) when the power level from the<br />

“generator” on all phases falls below the selected trip point by at least the hysteresis value. The<br />

time delay is not used on the transition to the “not tripped” condition.<br />

The function is intended to detect conditions such as generator overload.<br />

Parameters<br />

The following parameters must be specified for the operation of the directional power (forward<br />

or export) relay::<br />

●<br />

(SPR-014) The maximum permitted power on any phase out of the “generator”.<br />

• (SPR-013) The maximum permitted system power out of the “generator”.<br />

●<br />

The time for which the directional power conditions must be true.<br />

●<br />

The power level below the previously defined maximum that all phases from the<br />

“generator” must exceed to return operation to the not tripped condition following a<br />

trip. (Hysteresis)<br />

Parameter details<br />

Range of Directional Power trip (TripPoint) 3 — 120% of nominal power per phase (line)<br />

Range of Hysteresis (Diff)<br />

1 — 15% of nominal power per phase<br />

Range of Time Delay (TimeDelay) 0 to 30 seconds<br />