Parameter details<br />
Range of Phase Difference (PhAngle)<br />
Range of Voltage Difference (VDelta)<br />
Minumum Voltage Level (Vmin)<br />
Range of Bus Voltage Trip point<br />
Range of Time Delay (TimeDelay)<br />
Range of slip frequency (SlipFreq)<br />
Voltage Accuracy<br />
2 — 20 degrees<br />
0 — 20% of nominal input voltage<br />
5-119% of nominal input voltage<br />
5 — 50% of nominal input<br />
0 to 5 seconds<br />
0.1 — 1 Hz<br />
± 2% of nominal input voltage<br />
There is a relationship between the phase angle <strong>and</strong> the slip frequency settings. When one<br />
parameter is adjusted, the setting range of the other may be automatically adjusted to prevent a<br />
condition where the relay may never close.<br />
CAUTION: This trip relay can be configured to Latch. This feature may be<br />
undesirable, if enabled in error.<br />
TYPE 27 — UNDER VOLTAGE<br />
Brief details<br />
The relay will operate (trip) when the signal level on any of the “generator” voltage inputs is<br />
less than the selected value for the duration of the time delay. The relay will return to the “not<br />
tripped” condition (provided that latched operation has not been selected) when all “generator”<br />
voltage inputs rise above the selected trip point by at least the hysteresis value. The time delay<br />
is not used on the transition to the “not tripped” condition.<br />
Parameters<br />
You must specify the following parameters for operation of the under voltage relay:<br />
●<br />
The minimum permitted voltage on any of the voltage inputs from the “generator”.<br />
●<br />
The time for which the under voltage conditions must be true.<br />
●<br />
The voltage above the previously defined minimum that all inputs from the “generator”<br />
must exceed to return operation to the not tripped condition following a<br />
trip. (Hysteresis)<br />
Range of Voltage Trip point (Trip Point)<br />
Range of Diff (Diff)<br />
Range of Time Delay (TimeDelay)<br />
5-119% of nominal input<br />
1 — 15% of nominal input<br />
0 to 30 seconds<br />