Time over current characteristics<br />

The response time of the relay when operating in Time Over Current mode may determined<br />

using the relationship:<br />

Time-Current Characteristic k1 k2 k3<br />

St<strong>and</strong>ard Inverse 0.01414 0.02 0.1<br />

Very Inverse 1.3636 1 0.1<br />

Extremely Inverse 8.0808 2 0.1<br />

Long time st<strong>and</strong>by Earth Fault 12.121 1 0.1<br />

The curves describing these characteristics may be found on the following pages (Figs 4 to 7).<br />

Limits of operation<br />

The maximum “Multiple of trip setting” applicable for a trip setting at “nominal input” (e.g. Trip<br />

point at 5 Amps on a 5 Amp unit) is 5. “Multiple of trip setting” values of greater than 5 are only<br />

valid for trip levels of less than “nominal input”. This parameter is limited by the dynamic range<br />

of the current input circuits which start to limit above 5 times “nominal” input.<br />

The maximum time delay introduced by the Time-Current characteristics is limited by the<br />

resolution of the current input in the region of the trip point. This limits the “Multiple of trip<br />

setting” to approximately 1.007.<br />