13.01.2015 Views

Installation and Operating Instructions - Crompton Instruments

Installation and Operating Instructions - Crompton Instruments

Installation and Operating Instructions - Crompton Instruments

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SERIAL COMMUNICATIONS<br />

Modbus RTU<br />

Parameter<br />

Values<br />

Media<br />

3 Wire, (A, B, Ground) RS485<br />

Multidrop<br />

32 St<strong>and</strong>ard Loads,<br />

SPR = 1 St<strong>and</strong>ard Load<br />

Protocol<br />

Modbus RTU<br />

Baud Rate 2400/4800/9600/19200<br />

Parity<br />

Odd/Even/None<br />

Stop Bits 1 or 2<br />

Response Time<br />

150 mSec (Max), 80mSec (Typical)<br />

Register Representation 4 Byte IEEE 754, represented as register pairs,<br />

big endian byte order - can be reversed<br />

Functions Supported Read Input Registers ( 04)<br />

Read Holding Registers (03)<br />

Write Holding Registers (16)<br />

Exception Codes Illegal function (01)<br />

Illegal Data Address ( 02)<br />

Illegal Data Value ( 03)<br />

SPECIFICATION APPROVAL<br />

UL <strong>and</strong> CSA recignised File No. E214293<br />

Railtrack Certificate of Acceptance<br />

PA051/1450. Scope: Protective Device<br />

on Signalling Power Supply Systems<br />