REAL TIME CLOCK<br />
Accuracy<br />
Ageing<br />
Resolution<br />
Battery Type<br />
Battery Life (No auxiliary)<br />
± 1 minute per month<br />
± 3 ppm (parts per million) per year<br />
0.1 seconds<br />
Lithium (Return product to factory<br />
for replacement)<br />
3 years<br />
MEASURING RANGES<br />
Values of measured quantities for which errors are defined.<br />
Voltage 20 … 120%<br />
Current 20 ….. 120% (functional 5%...500%)<br />
Frequency<br />
45 … 66 Hz<br />
Active power (Watt) 5 ….. 120%<br />
Power Factor<br />
0.5..1..0.5, Importing or Exporting<br />
ACCURACY AND RESOLUTION<br />
The electrical measurements <strong>and</strong> trip functions have the following accuracy levels. The<br />
resolution of these settings or measurements will change dynamically, depending on any PT or<br />
CT ratio settings. Under some operating conditions, occasionally single values observed via<br />
modbus may lie slightly outside specified accuracy limits. However preceding <strong>and</strong> succeeding<br />
values will be within specified limits.<br />
Voltage<br />
Accuracy<br />
+/- 1% of nominal input voltage<br />
Resolution 0.1 Volt for system Voltages of 57.7 to 999.9V<br />
1 Volt for system Voltages of 1kV to 9.999kV<br />
10 Volt for system Voltages of 10kV to 99.99kV<br />
100 Volt for system Voltages of 100kV to 400kV<br />
Current<br />
Accuracy<br />
Resolution<br />
Frequency<br />
Accuracy<br />
Resolution<br />
+/- 2.5% of nominal input<br />
0.01A for system currents of 0.01 A to 99.99 Amps<br />
0.1A for system currents of 100 A to 999.9 Amps<br />
1A for system currents of 1 kA to 9.999 kA<br />
+/- 0.03 Hz of nominal<br />
0.01 Hz<br />
91