Maintenance Instructions<br />
B.7 Causes with frequent impeller waste<br />
The impeller of the cooling water pump must be regarded as wearing part. The life span of the<br />
impeller can be extremely different and exclusively depends on the operating conditions. The<br />
cooling water pumps of the PANDA generators are laid out in such a way that the number of revolutions<br />
of the pump lies low compared with other aggregates. This is for the life span of the pump<br />
a positive effect. Unfavorably affects the life span of the impeller, if the cooling water sucking in<br />
way is relatively long or the supply is handicapped, so that the cooling water sucking in range<br />
develops a negative pressure. This can reduce first of all the power of the cooling water pump<br />
extremely that the wings of the impeller are exposed to very strong loads. This can shorten the<br />
life span extremely. Further the operation of the impeller pump loaded in waters with a high portion<br />
of suspended matters. The use of the impeller pump is particularly critical in coral waterbodies.<br />
Cases are well-known, which a impeller pump had so strongly run after 100 hours already<br />
that the lip seal on the wave was ground in. In these cases sharp crystal parts of the coral sand<br />
assess in the rubber seal and affect like an abrasive the high-grade steel shank of the impeller<br />
pump. If the generator were mounted over the water level it is particularly unfavorable for the<br />
impeller pump. After the first start some seconds will pass by, until the impeller can suck in cooling<br />
water. This short unlubricated operation time damages the impeller. The increased wear can<br />
lead after short time to the loss. (see special notes: "Effects on the impeller pump, if the generator<br />
is mounted over the waterline")<br />
B.7.1 Exchange of the impeller<br />
Close the raw water stop cock.<br />
Raw water pump on the front side of the<br />
genset.<br />
Page 22 <strong>PMS</strong>_<strong>4500</strong>_<strong>FCB</strong>_manual.V02 - Chapter B: Maintenance Instructions 15.7.05