Installation Instructions<br />
D.5 Watercooled Exhaust System<br />
By injecting the outlet seawater into the exhaust manifold, the exhaust gases are cooled and the<br />
noise emissions from the exhaust system are reduced.<br />
D.5.1<br />
Installation of the standard exhaust system<br />
The generator exhaust system must remain completely independent and separate from the<br />
exhaust system of any other unit(s) on board. The exhaust hose has an inner diameter of 30mm.<br />
The water lock must be installed at the lowest point of the exhaust system. An optional noise<br />
insulated water lock can also be installed. The exhaust hose descends from the capsule to the<br />
water lock. Then the hose rises via the "goose neck" to the silencer (see drawing). The goose<br />
neck must be vertical and sit preferably along the ship's keel centre line. The exhaust system<br />
must be installed so that the back pressure inside the exhaust does not exceed 0.4 bar (6 psi)<br />
and total length does not exceed 6m (20 ft.).<br />
Exhaust diameter see Table F.3, “Technical Data Generator,” on page VI.<br />
1. Generator<br />
2. Water lock<br />
3. Goose neck<br />
4. Silencer<br />
5. Hull outlet<br />
Page 48 <strong>PMS</strong>_<strong>4500</strong>_<strong>FCB</strong>_manual.V02 - Chapter D: Installation Instructions 15.7.05