PMS 4500 FCB Manual - Ysebaert
PMS 4500 FCB Manual - Ysebaert
PMS 4500 FCB Manual - Ysebaert
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Installation Instructions<br />
D.8.2<br />
Installation AC-Box / distribution panel separate connected<br />
1. Generator<br />
2. Starter battery<br />
3. AC-Control box<br />
4. Distribustion box<br />
5. Remote control panel<br />
6. Fuel pump<br />
All electrical safety installations have to be made on board.<br />
A power source selector switch must be installed between the generator (or if applicable,<br />
AC-Control box) and the ship´s electrical supply system. This switch must used to ensure<br />
that all AC consumers can be switched off at once. This switch should also be installed to<br />
keep the generator and shore (grid) power systems separate.<br />
A 3-way cam-type switch should be used. This switch basic positions:<br />
"Shore power" - "OFF" - "Generator". If an (DC-AC) inverter is used, a<br />
fourth position will be required.<br />
0. OFF<br />
I. Generator<br />
II. Shore power connection<br />
III. Inverter<br />
Page 58 <strong>PMS</strong>_<strong>4500</strong>_<strong>FCB</strong>_manual.V02 - Chapter D: Installation Instructions 15.7.05