Installation Instructions<br />

Anti-freeze<br />

In the interest of safety, the freezing point of the closed circuit coolant should be checked on<br />

regular basis. Be sure that the coolant/antifreeze mixture is good for at least -15°C (5°F) and if is<br />

possible that your genset experiences lower temperatures, for example during storage or transportation,<br />

then the entire cooling system should be drained and purged. To purge the cooling<br />

system, compressed air at about 0.5 bar (7.5 psi) is sufficient.<br />

Again de-aerating process in the few days after the first startup<br />

Also after the first implementing a small amount of air can be reside in the cooling circuit. To<br />

ensure an imaculate und actual operating of the cooling system the de-aerating process must be<br />

repeated casual in the next few days (if necessary weaks). Small amount of air will be still exit out<br />

of the de-aerating openings especially if the generator stood still for a long time.<br />

ATTENTION! During the de-aerating process it must be checked again and again if the<br />

cooling water is indeed circulating. If air bubbles established in the internal cooling water<br />

pump, it could be, that the cooling water circuit is not circulate. Then the generator would<br />

be warming very fast and switched off by overheating.<br />

D.4.5<br />

Pressure test for control of cooling water circuit<br />

Check with the hand if a temperature difference exists whether between cooling water in-flow and<br />

cooling water return.<br />

Feel the cooling water in-flow line at the internal cooling water pump.<br />

Feel the cooling water return pipe either at the outlet of the water-cooled exhaust elbow union or<br />

at the side, where this pipe entry at the heat exchanger.<br />

The temperature difference between in-flow and return is approx 10 degrees.<br />

15.7.05 <strong>PMS</strong>_<strong>4500</strong>_<strong>FCB</strong>_manual.V02 - Chapter D: Installation Instructions Page 47