7<br />
Flue gas installation<br />
7.2 Flue termination<br />
The following details refer to all flue systems.<br />
a. The terminal must be positioned such that the <strong>pro</strong>ducts<br />
of combustion can disperse freely at all times.<br />
b. A plume of water vapour will sometimes be visible<br />
from the flue terminal. Positions where this could be a<br />
nuisance should be avoided.<br />
c. If the terminal is fitted less than 2 m above a balcony,<br />
above ground or above a flat roof to which people<br />
have access then a suitable terminal guard must be<br />
<strong>pro</strong>vided and fitted (contact Tower Flue Components,<br />
Tonbridge, TN9 1TB).<br />
i Vertical<br />
flues must not terminate within<br />
600 mm of an openable window, air vent or any<br />
other ventilation terminal.<br />
The flue system shall be so placed or shielded as to prevent<br />
ignition or damage to any part of the building.<br />