13 Troubleshooting<br />

Code Meaning Cause<br />

F.68 Unstable flame signal fault Air in gas, gas flow pressure too low, wrong air ratio, condensate route<br />

blocked, wrong gas restrictor, ionisation flow interruption (cables, electrodes),<br />

flue gas recirculation, condensate route<br />

F.70 Invalid device specific number (DSN) Spare part case: Display and PCB changed at the same time and appliance<br />

code not reset<br />

F.71 Flow NTC fault Flow temperature sensor signalling constant value:<br />

- Flow temperature sensor incorrectly positioned at supply pipe.<br />

- Flow temperature sensor defective.<br />

F.72 Flow/return NTC fault Flow/return NTC temperature difference too great -> flow and/or return<br />

temperature sensor defective<br />

F.73 Water pressure sensor signal in the wrong range<br />

(too low)<br />

F.74 Water pressure sensor signal outside correct<br />

range<br />

(too high)<br />

F.75 Fault, no pressure change detection when starting<br />

pump<br />

F.76 Overheating <strong>pro</strong>tection on primary heat<br />

exchanger has responded<br />

Interruption/short circuit of water pressure sensor, interruption/short circuit<br />

to GND in supply line to water pressure sensor or water pressure sensor<br />

defective<br />

Cable to water pressure sensor has short-circuited at 5 V/24 V<br />

or internal fault in water pressure sensor<br />

Water pressure sensor and/or pump defective, air in heating installation,<br />

too low water pressure in boiler; check adjustable bypass, connect external<br />

expansion vessel to return<br />

Cable or cable connections for safety fuse in primary heat exchanger or<br />

primary heat exchanger defective<br />

F.77 Flue non-return flap/condensate pump fault No response from flue non-return flap or condensate pump defective<br />

F.78 Interruption to DHW outlet sensor at external<br />

controller<br />

UK link box is connected, but hot water NTC not bridged<br />

F.83 Flow and/or return temperature sensor temperature<br />

change fault<br />

F.84 Fault: Flow/return temperature sensor temperature<br />

difference implausible<br />

F.85 Fault: Flow and return temperature sensors incorrectly<br />

fitted<br />

connection<br />

When the burner starts, the temperature change registered at flow and/or<br />

return temperature sensor is non-existent or too small.<br />

- Not enough water in the boiler<br />

- Flow and/return temperature sensor not in correct position at pipe.<br />

Flow and return temperature sensors returning implausible values.<br />

- Flow and return temperature sensors have been inverted.<br />

- Flow and return temperature sensors have not been correctly fitted.<br />

Flow and/or return temperature sensors<br />

have been fitted to the same pipe/wrong pipe.<br />

No communication with the PCB Communication fault between display and PCB in the electronics box<br />

13.2 Fault codes (continued)<br />

13.3 Running test <strong>pro</strong>grams<br />

By activating various test <strong>pro</strong>grams, you can trigger special<br />

functions on the boiler (¬ table. 10.1). The display shows<br />

which test <strong>pro</strong>gram you have chosen.<br />

> Read how to start the test <strong>pro</strong>grams in ¬ section 10.2.<br />

13.4 Resetting parameters to factory settings<br />

As well as the option to manually reset individual parameters<br />

to the default settings specified in ¬ table 11.1, you can<br />

also reset all parameters at once.<br />

> Set the value of the diagnosis code parameter D.096 to<br />

"1" (¬ section 11.1).<br />

You have now reset all parameters to factory settings.<br />