13 Troubleshooting<br />
Code Meaning Cause<br />
F.68 Unstable flame signal fault Air in gas, gas flow pressure too low, wrong air ratio, condensate route<br />
blocked, wrong gas restrictor, ionisation flow interruption (cables, electrodes),<br />
flue gas recirculation, condensate route<br />
F.70 Invalid device specific number (DSN) Spare part case: Display and PCB changed at the same time and appliance<br />
code not reset<br />
F.71 Flow NTC fault Flow temperature sensor signalling constant value:<br />
- Flow temperature sensor incorrectly positioned at supply pipe.<br />
- Flow temperature sensor defective.<br />
F.72 Flow/return NTC fault Flow/return NTC temperature difference too great -> flow and/or return<br />
temperature sensor defective<br />
F.73 Water pressure sensor signal in the wrong range<br />
(too low)<br />
F.74 Water pressure sensor signal outside correct<br />
range<br />
(too high)<br />
F.75 Fault, no pressure change detection when starting<br />
pump<br />
F.76 Overheating <strong>pro</strong>tection on primary heat<br />
exchanger has responded<br />
Interruption/short circuit of water pressure sensor, interruption/short circuit<br />
to GND in supply line to water pressure sensor or water pressure sensor<br />
defective<br />
Cable to water pressure sensor has short-circuited at 5 V/24 V<br />
or internal fault in water pressure sensor<br />
Water pressure sensor and/or pump defective, air in heating installation,<br />
too low water pressure in boiler; check adjustable bypass, connect external<br />
expansion vessel to return<br />
Cable or cable connections for safety fuse in primary heat exchanger or<br />
primary heat exchanger defective<br />
F.77 Flue non-return flap/condensate pump fault No response from flue non-return flap or condensate pump defective<br />
F.78 Interruption to DHW outlet sensor at external<br />
controller<br />
UK link box is connected, but hot water NTC not bridged<br />
F.83 Flow and/or return temperature sensor temperature<br />
change fault<br />
F.84 Fault: Flow/return temperature sensor temperature<br />
difference implausible<br />
F.85 Fault: Flow and return temperature sensors incorrectly<br />
fitted<br />
connection<br />
When the burner starts, the temperature change registered at flow and/or<br />
return temperature sensor is non-existent or too small.<br />
- Not enough water in the boiler<br />
- Flow and/return temperature sensor not in correct position at pipe.<br />
Flow and return temperature sensors returning implausible values.<br />
- Flow and return temperature sensors have been inverted.<br />
- Flow and return temperature sensors have not been correctly fitted.<br />
Flow and/or return temperature sensors<br />
have been fitted to the same pipe/wrong pipe.<br />
No communication with the PCB Communication fault between display and PCB in the electronics box<br />
13.2 Fault codes (continued)<br />
13.3 Running test <strong>pro</strong>grams<br />
By activating various test <strong>pro</strong>grams, you can trigger special<br />
functions on the boiler (¬ table. 10.1). The display shows<br />
which test <strong>pro</strong>gram you have chosen.<br />
> Read how to start the test <strong>pro</strong>grams in ¬ section 10.2.<br />
13.4 Resetting parameters to factory settings<br />
As well as the option to manually reset individual parameters<br />
to the default settings specified in ¬ table 11.1, you can<br />
also reset all parameters at once.<br />
> Set the value of the diagnosis code parameter D.096 to<br />
"1" (¬ section 11.1).<br />
You have now reset all parameters to factory settings.<br />
58 Installation and maintenance instructions <strong>ecoTEC</strong> <strong>pro</strong> 0020129672_03