13.11.2012 Views

ecoTEC pro - Vaillant

ecoTEC pro - Vaillant

ecoTEC pro - Vaillant

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

12.1 Measuring the CO2 concentration<br />

i<br />

The boiler is fitted with a flue gas analysis point<br />

(1). A suitable flue gas analyser can be connected<br />

to this point to establish the combustion<br />

performance of the boiler.<br />

> Remove the front casing (¬ section 4.7).<br />

> Start the testing <strong>pro</strong>gram P.01 (¬ section 10.2).<br />

> Wait at least 5 minutes until the boiler reaches its operating<br />

temperature.<br />

> Measure the CO2 concentration at the flue gas analysis<br />

point (1). Compare the measured value with the corresponding<br />

value in ¬ table 12.1.<br />

> If all these points are as required, <strong>pro</strong>ceed as described<br />

in ¬ section 12.2.<br />

> If one of the flue gas values is greater than the acceptable<br />

values in ¬ table 12.1, then <strong>pro</strong>ceed as described in<br />

the following ¬ section 12.1.4.<br />

12.1.4 Adjusting the CO2 concentration (or the air<br />

ratio)<br />

a<br />

Danger!<br />

Increased risk of poisoning due to incorrect<br />

settings!<br />

If one of the flue gas values is greater than<br />

the acceptable values in ¬ table 12.1 then:<br />

> Check the integrity of the complete flue<br />

gas installation.<br />

> Check the integrity of the combustion<br />

circuit seals.<br />

> Check the gas inlet working pressure.<br />

> Check the gas flow rate.<br />

1<br />

Inspection and maintenance 12<br />

12.2 Removing the covering cap for the air ratio setting adjusting<br />

screw (gas setting) and making the air ratio setting<br />

If the flue gas value needs to be adjusted, <strong>pro</strong>ceed as<br />

follows.<br />

The adjusting screw for making the air ratio setting is<br />

located beneath a blue covering cap (1), which is easy to<br />

remove.<br />

> Remove the yellow sticker.<br />

> Remove the covering cap.<br />

> Set the relevant CO2 value (value with removed front<br />

casing ¬ table 12.1) by turning the screw (2). Use a<br />

2.5 mm Allen key for this.<br />

– Turn to the left: higher CO2 concentration,<br />

– Turn to the right: lower CO2 concentration.<br />

i Natural<br />

i Liquid<br />

gas: Only perform the adjustment in<br />

small increments of 1/8 turn and wait ap<strong>pro</strong>ximately<br />

1 minute after each adjustment until the<br />

value stabilises.<br />

gas: Only perform the adjustment in very<br />

small increments (ap<strong>pro</strong>ximately 1/16 turns), and<br />

wait ap<strong>pro</strong>ximately 1 minute after each adjustment<br />

until the value stabilises.<br />

> Press the "Cancel" selection button once the settings<br />

have been adjusted.<br />

> When the adjusting work is complete, put the covering<br />

cap back on again.<br />

> Put the front casing back on (¬ section 4.7).<br />

Installation and maintenance instructions <strong>ecoTEC</strong> <strong>pro</strong> 0020129672_03 47<br />

1<br />

2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!