11<br />

Adapting the boiler to the heating installation<br />

Code Parameters Adjustable values<br />

D.027 Switching of relay 1 on the<br />

"2 in 7" multi-functional module VR 40<br />

D.028 Switching of relay 2 on the<br />

"2 in 7" multi-functional module VR 40<br />

1 = Circulation pump<br />

2 = External pump<br />

3 = Cylinder charging pump<br />

4 = Extractor hood<br />

5 = External solenoid valve<br />

6 = External fault message<br />

7 = Solar pump (not active)<br />

8 = Remote control eBUS (not active)<br />

9 = Legionella <strong>pro</strong>tection pump (not active)<br />

10 = Collective solar valve (not active)<br />

1 = Circulation pump<br />

2 = External pump<br />

3 = Cylinder charging pump<br />

4 = Extractor hood<br />

5 = External solenoid valve<br />

6 = External fault message<br />

7 = Solar pump (not active)<br />

8 = Remote control eBUS (not active)<br />

9 = Legionella <strong>pro</strong>tection pump (not active)<br />

10 = Collective solar valve (not active)<br />

Factory<br />

setting<br />

2<br />

Your own<br />

setting<br />

D.033 Fan speed target value In rpm Not adjustable<br />

D.034 Fan speed actual value In rpm Not adjustable<br />

D.035 Position of the diverter valve 0 = Heating; 100 = Hot water; 40 = Mid-position Not adjustable<br />

D.036 Hot water flow quantity<br />

(impeller sensor)<br />

In l/min Not adjustable<br />

D.039 Solar feed temperature Actual value in °C Not adjustable<br />

D.040 Flow temperature Actual value in °C Not adjustable<br />

D.041 Return temperature Actual value in °C Not adjustable<br />

D.044 Digitised ionisation value Display range 0 to 1020,<br />

> 800 no flame<br />

< 400 good flame<br />

40 Installation and maintenance instructions <strong>ecoTEC</strong> <strong>pro</strong> 0020129672_03<br />

2<br />

Not adjustable<br />

D.046 Pump type Not relevant Not adjustable<br />

D.047 Outside temperature (with weathercontrolled<br />

<strong>Vaillant</strong> controller)<br />

Actual value in °C Not adjustable<br />

D.050 Offset for minimum speed In rpm, setting range: 0 to 3000 Nominal value<br />

set in factory<br />

D.051 Offset for maximum speed In rpm, setting range: -990 to 0 Nominal value<br />

set in factory<br />

D.058 Activation of solar post-heating for VUW<br />

boilers;<br />

Switch hot water mode<br />

0: Solar post heat mode deactivated<br />

3: DHW activation target value minimum 60 °C<br />

D.060 Number of temperature limiter shutdowns<br />

Number of shutdowns Not adjustable<br />

D.061 Number of ignition device cutoffs Number of unsuccessful ignitions in the last attempt Not adjustable<br />

D.064 Average ignition time In seconds Not adjustable<br />

D.065 Maximum ignition time In seconds Not adjustable<br />

11.1 Diagnosis codes (continued)<br />