FunctionError message Meaning Steps to be takenSystem connection?Connection PE?Device error xNo low-resistanceconnection of terminalsL1, L2 tothe IT systemNo low-resistanceconnection of theterminals andKE to earth (PE)Internal deviceerror1. Check the wiring of terminal L1, L2 tothe IT system2. Press the test button3. Switch the supply voltage off and on.4. Check the fuses1. Check wiring of terminal and KE toearth (PE)2. Press TEST button3. Switch the supply voltage off and on1. Press TEST button2. Switch the supply voltage off and on3. Contact BENDERIf the on/off switching of the supply voltage is not possible for technicalreasons, a RESET of the process control can be carried out by pressingthe "ESC“, "RESET“ and "MENU“ key.16 TGH1352en/11.2004