Serial interfaces6.4.2 BMS SlaveAll <strong>IRDH375</strong>B are factory set to slave mode (address 3). In a BMS network,one address must be selected from the address range 2...30 for each slave.There may be no gaps of more than five subsequent addresses, so that allslaves can be scanned by the Master. For <strong>IRDH375</strong>B a BMS address can beselected from the address range 1 ... 30. When assigning the addresses, alsoother devices such as the EDS47x-12 must be considered.The correct reception of BMS data is indicated by a flashing point on the displayon the right of the measuring pulse indication.***IT-SYSTEM***R+=500KFlashing point:BMS data receivedIf no flashing point appears, it may be attributed to the following:• no Master available in the network• more than one Master available in the network• RS485 interface (terminal A/B) not connected or reversed58 TGH1352en/11.2004