ConnectionIn case of current-controlled intermediate circuits of frequency converters,higher DC voltages are to be expected.The given voltage values for AC/DC systems take into account values foundby previous experience (factor 1.414 between DC voltage and AC voltage).The maximum DC voltage in case of insulation faults in the DC part of theIT system, for example converter intermediate circuit, is DC 1840 V. Fromthis, the maximum nominal AC voltage is calculated:U max = DC 1840 V / 1.414 = AC 1300 VTGH1352en/11.200431