Commissioning flow chart (threepart)Commissioning of the A-ISOMETER® (3)In order to check the properconnection, a functional testusing a suitable resistance isto be carried out.Size of the resistance:50% of the preset responsevalue Alarm 2.Do both alarm LEDs light up?Did the alarm relays switch ?yesnoCheck the connecting leads !Is voltage Un applied to theterminals L1/L2 ?When a coupling device isused, is it correctly connected ?Check the voltages with a voltmeteDo both alarm LEDs light ?Did the alarm relays switch?Remove the resistor !yesAlarm LEDs extinguished ?Did the output relays changetheir position ?noyesThe <strong>IRDH375</strong> is correctlyconnected and functions reliably !24 TGH1352en/11.2004