A-ISOMETER® IRDH375 IRDH375B - Bender
A-ISOMETER® IRDH375 IRDH375B - Bender
A-ISOMETER® IRDH375 IRDH375B - Bender
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
6. Serial interfacesThe A-ISOMETERs® <strong>IRDH375</strong> and <strong>IRDH375</strong>B have differently designed serialinterfaces.<strong>IRDH375</strong><strong>IRDH375</strong>B- RS485 and IsoData protocol- not galvanically isolated- ASCII, unidirectional- RS485 and BMS protocol- galvanically isolated- ASCII, bidirectional6.1 RS485 interface with IsoData protocol (<strong>IRDH375</strong>)Data transmission is continuously carried out and can neither be interruptedby the data slave station nor be influenced in any other way. This protocolcannot be used in combination with the BMS protocol.For data evaluation via PC or Laptop, the terminal software "IsoData" and aninterface converter of the ASCII-RS485/RS232 type is required.Interface data:• RS485 interface galvanically isolated from the device electronics• Connection to terminal A and B• Maximum cable length 1200 m• Transmission protocol 9600 baud - 1 start bit - 1 stop bit - 8 data bit• After each valid measurement, the following data block is provided:TGH1352en/11.200453