Operation and setting5.5 Menu ISO ADVANCED: Setting of the extended functions5.5.1 External coupling devices (AGH: no)Basic setting "no", when no coupling device is used (factory setting).AGH: 204 AK80Terminal AK of the <strong>IRDH375</strong> is connected to terminal AK80 of theAGH204S-4. The nominal voltage range is extended to 3AC 0...1650 V. Onlycurrent converters with an output voltage not exceeding DC 1000 V are allowedto be connected (see "operation with coupling device" on page 30).AGH: 520STerminal AK of the <strong>IRDH375</strong> is connected to terminal 5 of the AGH520S.The nominal voltage range is extended to AC 0...7200 V. Only current converterswith an output voltage not exceeding DC 1000 V are allowed to beconnected.AGH: 204 AK160Terminal AK of the <strong>IRDH375</strong> is connected to terminal AK160 of theAGH204S-4. The nominal voltage range is extended to 3AC 0...1300 V. Onlycurrent converters with an output voltage not exceeding DC 0...1840 V areallowed to be connected (see "operation with coupling device" on page 30).AGH: 150 AK160Terminal AK of the <strong>IRDH375</strong> is connected to terminal AK160 of theAGH150W-4. The nominal voltage range is extended to DC 0...1760 V.The coupling monitoring is deactivated when an external couplingdevice is connected.TGH1352en/11.200445