Operation and setting5.9 Menu SERVICEThis menu item is provided for the BENDER service personnel and is protectedby a password against erroneous settings. It is intended to provide fastfault clearance by qualified experts in the event of a device error.5.10 Parameterization via InternetThe parameters of an <strong>IRDH375</strong>B indicated below can be checked and setfrom a remote place of use by using a personal computer. In addition, abrowser (viewing program for Internet application) and our protocol converterFTC470XET (BMS Ethernet/TCP/IP) are required.Remote setting is possible for:• Response value Alarm 1 (1...10,000 kΩ) (Y1)• Response value Alarm 2 (1...10,000 kΩ) (Y2)• Operating principle alarm relay 1 (e.g. N/O operation)• Operating principle alarm relay 2 (e.g. N/O operation)• Measuring principle (AMP or DC)• Current output ranges for external measuring instruments (0/4...20 mA)• Maximum system leakage capacitance (150 µF or 500 µF)• Time for repitition of the automatic self test (off/ 1 h/ 24 h• Starting time of the automatic self test (0.00...23.00 h)• Language of the alarm messages to be displayed (D, GB)• Setting the fault memory to ON or OFF52 TGH1352en/11.2004