LED STAT. DISPLAY DESCRIPTION CONSEQUENCEDisabled FAULT ON ZONE 01 A detector is missing from The detectors downstream ofFast/Fault Warehousezone no. 1, or zone no. 1 is the missing detector will beblink./Testshorted or openunable to signal fire conditionsLogic UnitThe Control panel is blocked The Control panel will be una-ONMains (red)Disab./FaultTelecomGround24V/24RFastblink.Fastblink.ONFastblink.FAULTMain FaultFAULTDL OutputFAULTGround FaultFAULT24V OutputFAULT24R Outputble to functionThe Control panel is NOT poweredThe batteries will provide po-from the Mains wer until they empty.The Dialler Output is shorted The Telephone devices set upor opento send fire warnings will beLeakage to Earth24V Output is shorted24R Output is shortedunable to functionThe Control panel functionsmay be impairedThe devices connected to the24V Output will be unable tofunctionThe devices connected to the24R Output will be unable tofunctionBattery Fastblink.FAULTBatteryThe Control panel batteries areempty, faulty or disconnectedThe Panel may be unable tofunction in the event of black-outDisab./FaultNAC FastFAULTNAC 1 OutputThe NAC1 Output is shorted oropenThe devices connected to theNAC1 will be unable to functionblink. FAULTNAC 2 OutputThe NAC2 Output is shorted oropenThe devices connected to theNAC2 will be unable to functionPeriph. Fast FAULTThe Panel CANNOT communicatewith the peripherals the status of the PeripheralsThe Panel will be unable to readblink. PeripheralThe information in the following rows is valid for Extinguishment Module nr. 1 and Extinguishment Module n. 2Fault: FAULT ON EXT. 1 The power supply to the Electrovalveis interrupted or the Electro-CANNOT be activatedThe Extinguishment devicesFastElectrovalvvalveOutput is shorted orELECTROVALVEblink.openFault:Pre Ext.Fault:ManualExt.Fault:Disab.Ext.Fault:Pres.SwitchFastblink.Fastblink.Fastblink.Fastblink.FAULT ON EXT. 1PRE-EXT. OUTPUTFAULT ON EXT. 1MANUAL EXT.INPUTFAULT ON EXT. 1INHIB.EXT.INPUTFAULT ON EXT. 1PRES.SWITCH INP.The Pre-extinguishment Outputis shorted or openThe Panel will be unable to signalthe Pre-extinguishment phaseManual Extinguishment Input The Manual Extinguishmentis shorted or openbuttons CANNOT activate theThe Inhibit ExtinguishmentInput is shorted or openThe Pressure switch Input isshorted or openFault:The Extinguishment Module isONLogic UnitblockedThe information in the following rows is valid for all the Power Supply StationsFAULT POWER ST.1 The Power Supply Station isMain Faultnot powered from the MainsFAULT POWER ST.1Low BatteryFAULT POWER ST.1Battery FaultFAULT POWER ST.1Battery Disconn.FAULT POWER ST.1OUT 1FAULT POWER ST.1OUT 2Extinguishment phaseThe Inhibit Extinguishmentbuttons CANNOT inhibit theExtinguishment phaseThe Panel will be unable to gaugethe Extinguishment GaspressureThe Extinguishment Modulewill be unable to functionThe batteries will supply thePower Supply Station untilthey emptyThe Power Supply Station batteriesThe Power Supply Station mayare lowbe unable to function in theevent of black-outThe Power Supply Station batteriesThe Power Supply Station mayare low or disconnected be unable to function in theevent of black-outThe batteries of the Power The Power Supply Station maySupply Station has shutdown be unable to function in thedue to voltage dropevent of black-outThe Output nr. 1 of the Power The devices connected to theSupply Station is shorted Output 1 will be unable to functionThe Output nr. 2 of the Power The devices connected to theSupply Station is shorted Output 2 will be unable to functionTable 1 Fault Descriptions

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!