EVENTS DETAILS DESCRIPTION24R OUT FAULT None 24R output shorted24R OUT RESTORE None 24R output previously shorted24V OUT FAULT None 24V output shorted24V OUT RESTORE None 24V output previously shortedALARM ZONE Zone no. + Description Zone no. is in Alarm statusAUTO UNBYPASSED Extinguishment Mod. nr. Automatic Extinguishment of Extinguishment Mod. nr. re-enabledBATT.CHARG.FAULT Power Supply Stat. nr. Charger of Power Supply Stat. nr. not operating properlyBATT.CHARG.REST. Power Supply Stat. nr. Charger of Power Supply Stat. nr. previously not workingBATTERY DISCONN. Power Supply Stat. nr. Batteries of Power Supply Stat. nr. disconnectedBATTERY FAULT None Panel batteries empty, malfunctioning or disconnectedBATTERY FAULT Power Supply Stat. nr. Batteries of Power Supply Stat. nr. empty or disconnectedBATTERY FAULT Power Supply Stat. nr. Batteries of Power Supply Stat. nr. lowBATTERY RECONN. Power Supply Stat. nr. Batteries of Power Supply Stat. nr. previously disconnectedBATTERY RESTORE Power Supply Stat. nr. Batteries of Power Supply Stat. nr previously lowBATTERY RESTORE None Panel batteries previously empty, malfunctioning or disconnectedBATTERY RESTORE Power Supply Stat. nr. Batteries of Power Supply Stat. nr. empty or disconnectedBUZZER SILENCED None Buzzer disabledBYPASSED ZONE Zone no. + Description Zone no. disabledDETECTOR MISSING Zone no. + Description A detector connected to zone no. is missingDIALLER ACTIVATE None Dialler Output activeDISAB.AUTOExtinguishment Mod. nr. Automatic Extinguishment of Extinguishment Mod. nr.i disabledDL OUT FAULT None Dialler connections interrupted or shortedDL OUT RESTORE None Dialler connections interrupted or shortedDL OUTPUT Enabled/Disabled The Dialler Output has been disabled/enabledEM ACTIVATED Extinguishment Mod. nr. EM Input of Extinguishment Mod. nr. activatedEM INPUT FAULT Extinguishment Mod. nr. EM Input of Extinguishment Mod. nr. shorted or openEM INPUT RESTORE Extinguishment Mod. nr. EM Input of Extinguishment Mod. nr. previously shorted or openEV OUT ACTIVATED Extinguishment Mod. nr. EV Output of Extinguishment Mod. nr. activatedEV OUT FAULT Extinguishment Mod. nr. EV Output of Extinguishment Mod. nr. shorted or openEV OUT RESTORE Extinguishment Mod. nr. EV Output of Extinguish. Mod. nr. previously shorted or openEVACUATE None Evacuation command executedGND FAULT REST. None Control panel ground fault restoredGROUND FAULT None Control panel leakage to EarthIE ACTIVATED Extinguishment Mod. nr. IE Input of Extinguishment Mod. nr. activatedIE INPUT FAULT Extinguishment Mod. nr. IE Input of Extinguishment Mod. nr. shorted or openIE INPUT RESTORE Extinguishment Mod. nr. IE Input of Extinguishment Mod. nr. previously shorted or openINVESTIGATION None Investigation DoneMAIN FAULTNone/Pow.SupStat.nr. Mains failure to Control panel/Power Supply Stat. nr.MAIN RESTORE None The Control panel/Power Supply Stat. nr. powered from MainsMANUAL BYPASSED Extinguishment Mod. nr. EM Input of Extinguishment Mod. nr. disabledMANUAL UNBYPASS. Extinguishment Mod. nr. EM Input of Extinguishment Mod. nr re-enabledMODE Night/Day Control panel switched from Night to Day ModeNAC OUTPUT Enabled/Disabled One of the Alarm outputs has been disabled/enabledNAC1 FAULT None Alarm device connections interrupted or shortedNAC1 RESTORE None Alarm device connections interrupted or shortedNAC2 FAULT None Alarm device connections interrupted or shortedNAC2 RESTORE None Alarm device connections interrupted or shortedOUT 1 RESTORE Power Supply Stat. nr. O1 Output of Power Supply Stat. nr shortedOUT 1 SHORT Power Supply Stat. nr. O1 Output of Power Supply Stat. nr shortedOUT 2 RESTORE Power Supply Stat. nr. O2 Output of Power Supply Stat. nr shortedOUT 2 SHORT Power Supply Stat. nr. O2 Output of Power Supply Stat. nr shortedOUTS BYPASSED Extinguishment Mod. nr. Extinguishment Mod. PR, EV and AV outputs disabledOUTS UNBYPASSED Extinguishment Mod. nr. Extinguishment Mod. PR, EV and AV outputs re-enabledPE OUT ACTIVATED Extinguishment Mod. nr. PR Output of Extinguishment Mod. nr. activatedPE OUT FAULT Extinguishment Mod. nr. PR Output of Extinguishment Mod. nr. shorted or openPERIPHERAL FAULT Peripheral type and nr. The device concerned missing or faultyPERIPHERAL REST. Extinguishment Mod. nr. PR Output of Extinguish. Mod. nr. previously shorted or openPERIPHERAL REST. Device type+Number The device concerned previously missing or faultyTable 2 Event Descriptions (Continues ...): AV = Extinguishment Done; EM = Manual Extinguishment; EV = Electrovalve;IE = Inhibit Extinguishment ; PR = Pre-extinguishment; PS = Pressure switch.6 Conventional Fire Panels J424/J408

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!