4. Go back to step 1 to program another Output optionor, press the Next phase key 9 to go to the followingProgramming Phase (see Column A).The “PANEL” Programming PhaseThe PANEL LED will blink to indicate that the system isready to program the User Code, Day and Night ModeTimes and current Time and Date. During this phase,the keys and LEDs will operate in accordance with theoptions preceded by in the panes on the ProgrammingOverlay, see Figure 32.1. Using the keys in columns C and D, select the parameteryou want to program (refer to the respectiveparagraph for details) or, press the Next phasekey 9 to go to the following Programming Phase(see Column A). User Code (Key/LED 1)The LED will go On to indicate that the system is readyto start the programming procedure.Using keys 0 through 9, type in a 4 digit User Code. TheLED will go Off after entry of the fourth digit (indicatingthat the “User Code” has been accepted). Day Mode (Key/LED 2)The LED will go On to indicate that the system is readyto start the programming procedure.Using keys 0 through 9, type in the “Time” when thechangeover from Night to Day Mode must occur.Enter two digits for the Hour (00 to 23 — 00 for Midnight)and two for the Minutes (00 to 59). The LED willgo Off after entry of the fourth digit (indicating that thesetting has been accepted). Night Mode (Key/LED 4)The LED will go On to indicate that the system is ready tostart the programming procedure.Using keys 0 through 9, type in the “Time” (formatted asper Day Mode) when the changeover from Day to NightMode must occur. The LED will go Off after entry of the fourthdigit (indicating that the setting has been accepted). Clock (Key/LED 5)The LED will go On to indicate that the system is readyto start the programming procedure.Using keys 0 through 9, type in the current “Time” (formatas per Day Mode). Date (Key/LED 7)The LED will go On to indicate that the system is readyto start the programming procedure.Using keys 0 through 9, enter the respective two digitsfor the Day (00 to 31), Month (00 to 12) and Year (00 to99). The LED will go Off after entry of the last digit (indicatingthat the setting has been accepted).Wrong entries will be signalled by an audible error signal. Mains Off Delay (Key/LED 8)The LED will go On to indicate that the system is readyto start the programming procedure.Using keys 0 through 9, type in the length of time theControl panel must wait before signalling a Mains Failureevent.Enter four digits (0000 through 9999 minutes). The LEDwill go Off after entry of the last digit (indicating that the“Mains Off Delay” has been accepted).Wrong entries will be signalled by an audible error signal.The “VARIOUS” Programming PhaseThe VARIOUS LED will blink to indicate that the systemis ready to program the Stabilization Time, ResetTime, Silenceable Outs and Configuration 1 and 2.During this phase, the keys and LEDs will operate in accordancewith the options preceded by in the paneson the Programming Overlay, see Figure 33.1. Using the keys in columns C and D, select the parameteryou want to program, then refer to the respectiveparagraph or, press the Next phase key 9to go to the following Programming Phase (see ColumnA).MMM 640 sec - - Zone 1Zone 5 Pre-alarm time Refresh time Zone 1 Zone 5128 sec AlarmPre-alarmFaultAlarm verific. 1 2 3MMM 320 secMODULESUser code Day modeALARM 64 secStabilization time Reset timeExting. 1 LCD 1 Power 1 Rep. 1Extinguish. time Zone 1/Exting. 1Zone 5Detect missingMMM 160 sec -- Zone 2Zone 6OC output Verification time Silence time Zone 2Zone 632 sec ResetDisablementTestSilen. Out R 4 5 6MMM VARIOUSALARMNight mode Clock16 secSilenceable outs Configuration 1 Exting. 2 LCD 2Power 2 Rep. 2Pre-alarm on RActivation zonesZone 2/Exting. 2Zone 6MMM - Zone 3Zone 7PANELNAC2 Alarm DL output delay Īncrease time Zone 3Zone 78 sec Double knockTest on NACs 7 8MMM OUTPUTSNAC1 Alarm DateMains off delay4 sec Configuration 2 Increase time Expander 1 LCD 3Power 3 Rep. 3Call-point alarmIncrease time Zone 3Zone 7MMM Next phase Next Option Zone 4Zone 8TIMESNAC2 Pre-alarmDecrease time Zone 4Zone 82 secNext OutputGas detector 9 0MMM 5 secZONESNAC1 Pre-alarm1 secDecrease time Expander 2 LCD 4Power 4 Rep. 4Decrease time Zone 4Zone 8A BCDE FFigure 33 The “VARIOUS” Programming Phase48 Conventional Fire Panels J424/J408

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!