DWORD m_port=3;DWORD m_address=1;DWORD m_timeout=100;DWORD m_checksum=0;Open_Com(COM3, 9600, Data8Bit, NonParity, OneStopBit);dwBuf[0] = m_port;dwBuf[1] = m_address;dwBuf[2] = 0x87024;dwBuf[3] = m_checksum;dwBuf[4] = m_timeout;dwBuf[5] = 1;dwBuf[6] = 1;AnalogOutReadBack_87K (dwBuf, fBuf, szSend, szReceive);Volt = fBuf[0];Close_Com(COM3);Remark:• ReadConfigurationStatus_87KDescription:This function is used to read configuration status of analog output module for I-87000series modules.Syntax:[ C ]WORD ReadConfigurationStatus_87K(DWORD dwBuf[], float fBuf[],char szSend[],char szReceive[])Parameter:dwBuf:DWORD Input/Output argument talbedwBuf[0] : [Input] COM port number, from 1 to 255dwBuf[1] :dwBuf[2] :dwBuf[3] :dwBuf[4] :[Input] Module address, form 0x00 to 0xFF[Input] Module ID, 0x87024[Input] 0= Checksum disable; 1= Checksum enable[Input] Timeout setting , normal=100 msecondLinPAC-8x4x SDK:196