PVC reclaimed water mains 14 inch to 20 inch diameter (14" - 20") shall be DR-18<br />

manufactured to ductile iron pipe outside dimensions and in compliance with AWWA C905.<br />

The pipe shall have an internal bell end and gasket seal with the joint in compliance with<br />

the requirements of ASTM D3139. The pipe color shall be Purple Pantone 522.<br />

HDPE reclaimed water main 4 inch to 16 inch in diameter (4” – 16”) shall be DR-11<br />

manufactured to ductile iron pipe outside dimensions and in compliance with AWWA C906,<br />

latest revision and ASTM F714. The pipe will be extruded from resin meeting specifications<br />

of ASTM D-3350 with a cell classification of type III, class C, category 5, grade P34<br />

polyethylene compound. The pipe color shall be Purple Pantone 522 or co-extruded Purple<br />

Pantone 522 color stripes.<br />

Ductile iron pipe shall be a <strong>minimum</strong> of Pressure Class 350. The Department reserves the<br />

right to require a different thickness class for unusual or non-standard laying conditions.<br />

The pipe shall be color coded with four (4)- 2"wide stripes along the length of the pipe at all<br />

four quadrants painted Purple Pantone 522. Pipe shall be cement lined as per<br />

ANSI/AWWA C104/A21.4.<br />

Ductile iron pipe shall conform to latest <strong>standards</strong> of ANSI/AWWA C150/A21.50 for the<br />

thickness <strong>design</strong> of ductile iron pipe and ANSI/AWWA C151/A21.51 for ductile iron pipe<br />

centrifugally cast in metal molds or sand-lined molds.<br />

Ductile iron pipe shall be cement lined per ANSI/AWWA C104/A21.4, flanged Pressure<br />

Class 53 with <strong>minimum</strong> wall thickness of 0.32 for 4-inch pipe and incremental increases of<br />

0.02” thickness for each pipe diameter increase up to 14-inches. Ductile iron pipe greater<br />

than 14-inches shall be submitted to the Department.<br />

All above ground DIP shall be coated with Pantone Purple 522 paint as follows:<br />

Sandblast and remove all paint and any loose material in accordance with SSPC SP-10.<br />

Sandblasting shall be performed using non-silca media. Do not paint or coat any<br />

nameplates, brass or stainless steel surfaces. Contractor shall use the following paint system<br />

or approved equal.<br />

TNEMEC<br />

1) Primer: TNEME-ALUMINUM MASTIC #135<br />

(3.0 to 5.0 mils DFT)<br />

2) Intermediate Series 66 Epoxoline<br />

Coat: Hi-Build Epoxy<br />

(4.0 to 6.0 mils DFT)<br />

3) Finish Series 73 Endura-Shield III<br />

49