c) Electrical Wiring<br />

1. Contractor shall utilize wiring supplied with the remote mount kit. Mount indicator<br />

(TR28) on the RCP. Wire is supplied and terminated from the meter head to the<br />

Indicator/Totalizer (TR28). Wire is also supplied to terminate at the RTU.<br />

2. Grounding<br />

Grounding system meeting a <strong>minimum</strong> resistance of 5 Ohms or less shall be<br />

installed at each transmitter location. Ground rods shall be 5/8” diameter X 8’0”<br />

copper clad steel. Connectors shall be solid copper clamps with connecting wire at<br />

least one size larger than any other wire on the same device. The number and<br />

pattern of ground rods shall be chosen to provide the required maximum resistance.<br />

d) Transmitter Indicator/Interface<br />

The flow transmitter (TR28) shall be connected to a device, the Indicator/Interface, in<br />

the Reuse Control Panel that interprets the digital signal and provides a signal that will<br />

interface with the control system and a visual display of the flow rate<br />

1. Mounting<br />

The Indicator/Interface will be supplied, installed and wired as part of the control<br />

panel by the RCP manufacturer and mounted on an inner dead-front door.<br />

2. Wiring<br />

All power supply, sensor, and interface output wiring shall be made in a work like<br />

manner conforming to the National Electric Code and local ordinances. All wiring<br />

shall be color-coded or tagged to maintain functionality and polarity. Any wire<br />

connections shall be made to screw type terminal strips using crimp on spade lug<br />

connections of the appropriate size.<br />

e) Start-up Procedure<br />

When the installation is complete, the equipment manufacturer’s representative shall<br />

verify that all the equipment has been installed and transmitter/monitors have been<br />

correctly programmed. With the system running, the equipment manufacturer’s<br />

representative verify output signals from each sensor, inputs to transmitter/monitors and<br />

correct transmitter outputs.<br />

1. A 8-hour time window (7days a week) for irrigation will be set at all site Reuse<br />

Control Panels, beginning at 10:00 PM and finished by 6:00 AM. <strong>Martin</strong> <strong>County</strong><br />

must approve any deviation from this schedule.<br />

65