12<br />

Parts specification<br />

Outdoor unit<br />

Specification of 3-pipe, heat recovery outdoor unit<br />

Model name MAR-F105HTM8-PE<br />

Cooling capacity kW 25.0 (28.0)<br />

Heating capacity kW 28.0 (31.5)<br />

Power supply<br />

Cooling<br />

380-415 V, 3 phase, 50 Hz<br />

Operating current A 17.4 (19.1)<br />

Power consumption kW 11.8 (12.8)<br />

EER 2.11 (2.19)<br />

Power factor<br />

Heating<br />

% 98 (97)<br />

Operating current A 17.7 (15.5)<br />

Power consumption kW 11.8 (10.5)<br />

COP 2.37 (3.0)<br />

Power factor % 96 (98)<br />

Starting current A 60<br />

Starting method Direct<br />

Sound level Sound pressure dB 58<br />

Sound power dB(A) 70<br />

Dimensions (H x W x D) mm 1700 x 990 x 790<br />

Net weight kg 285<br />

Colour Silky Shade (Munsell 1-Y8.5/0.5)/RAL 1013 (DE ~9)<br />

Compressor Type Hermetically sealed (twin scroll)<br />

Oil (volume) ml Polyolester NISSEKI RB74AF 74VG (7000)<br />

Crankcase heater Internal type<br />

Motor output kW 7.5<br />

Fan assembly Fan Propeller fan<br />

Motor output kW 0.4<br />

Air flow volume m3 /h 10,000<br />

Refrigeration (charged weight) kg R-407C (19)<br />

Piping connection Liquid mm 15.9 (flare connection)<br />

Discharge gas mm 19.0 (flare connection)<br />

Suction gas mm 28.6 (brazing connection)<br />

Max. equivalent piping length m 120<br />

Max. actual piping length m 100<br />

Max. piping head m 50: when the outdoor unit is installed above<br />

m 20: when the outdoor unit is installed below<br />

Suction accumulator case heater W 29 (240 V AC)<br />

Notes:<br />

1. Specifications are subject to change without notice.<br />

2. The specification shown in ( ) denotes operation with an indoor unit load diversity of 135%.<br />

3. Operating conditions:<br />

Outdoor temperature °C Cooling -5 to 43<br />

Heating -15 to 21<br />

Room temperature °C Cooling 18 to 32<br />

Heating 15 to 29<br />

4. Sound level: 1 m horizontal from centre.<br />

1.5 m vertical from base.