Additional refrigerant<br />
One <strong>Multi</strong> Controller<br />
Outdoor<br />
Two <strong>Multi</strong> Controllers<br />
Outdoor<br />
Three <strong>Multi</strong> Controllers<br />
Outdoor<br />
Four <strong>Multi</strong> Controllers<br />
Outdoor<br />
72<br />
X<br />
X<br />
L1<br />
L1<br />
Z<br />
Z<br />
Y<br />
Y<br />
L2<br />
L2<br />
L2<br />
Additional refrigerant<br />
M/C<br />
M/C<br />
M/C<br />
M/C<br />
L3<br />
L3<br />
L3<br />
L3<br />
Piping<br />
Indoor<br />
Indoor<br />
Indoor<br />
Indoor<br />
Table 1 - Branch pipes<br />
RAV-10* : 0.030 kg/m<br />
RAV-13* : 0.030 kg/m<br />
RAV-16* : 0.030 kg/m<br />
RAV-26* : 0.045 kg/m<br />
RAV-36* : 0.045 kg/m<br />
RAV-46* : 0.045 kg/m<br />
Example:<br />
RAV-464CH-PE � RAV-46*<br />
L1 = Main pipe (X + Y + Z)<br />
L2 = Sub pipe<br />
L3 = Branch pipe<br />
Pipe Additional gas/metre Additional gas<br />
MAR-F105 - main pipe L1 (X+Y+Z) (minus 2 m) x 0.19 kg/m =<br />
1st longest sub pipe L2 (minus 1 m) x 0.125 kg/m =<br />
2nd longest sub pipe L2 (minus 1 m) x 0.125 kg/m =<br />
1st longest branch pipe L3 (minus 2 m) x Refer to Table 1 =<br />
2nd longest branch pipe L3 (minus 2 m) x Refer to Table 1 =<br />
3rd longest branch pipe L3 (minus 2 m) x Refer to Table 1 =<br />
4th longest branch pipe L3 (minus 2 m) x Refer to Table 1 =<br />
5th longest branch pipe L3 (minus 2 m) x Refer to Table 1 =<br />
6th longest branch pipe L3 (minus 2 m) x Refer to Table 1 =<br />
7th longest branch pipe L3 (minus 2 m) x Refer to Table 1 =<br />
8th longest branch pipe L3 (minus 2 m) x Refer to Table 1 =<br />
Total additional gas charge = kg