Troubleshooting<br />

Diagnostic procedure for check code<br />

Check code Operation cause<br />

[Ad] 1. Fixed-speed compressor high pressure SW error.<br />

Fixed-speed compressor fault 2. Fixed-speed compressor IOL operation.<br />

3. Service valve closed.<br />

4. Outdoor fan, capacitor error.<br />

5. <strong>Multi</strong> Controller/outdoor PMV blockage.<br />

6. Outdoor heat exchanger blockage.<br />

7. SV2 circuit blockage.<br />

8. Miswiring of communicaiton between indoor and outdoor unit.<br />

9. Pd sensor error.<br />

10.Refrigerant overcharge.<br />

OCR: Overload Current Relay<br />

Does the fixed-speed high<br />

pressure switch operate?<br />

�<br />

Are the fixed-speed high<br />

pressure switch parts normal?<br />

�<br />

Is service valve fully open?<br />

�<br />

Does the outdoor fan<br />

normally operate?<br />

�<br />

Is there a problem with the<br />

outdoor unit heat exchanger?<br />

(1) Blockage of heat exchanger<br />

(2) Short circuit (air flow)<br />

(3) Blockage of air flow<br />

�<br />

C<br />

Yes<br />

Yes<br />

Yes<br />

Yes<br />

No<br />

No<br />

�<br />

Check parts.<br />

If defective, replace.<br />

Open service valve fully.<br />

No<br />

Yes<br />

�<br />

No<br />

No<br />

No<br />

�<br />

Repair failed position.<br />

�<br />

No<br />

Replace high pressure sensor.<br />

�<br />

Remove cause.<br />

�<br />

Are the connection, capacitor<br />

and fan motor normal?<br />

�<br />

Are the high pressure sensor<br />

characteristics normal?<br />

�<br />

Yes<br />

Yes<br />

No<br />

�<br />

See judgment flow of fixed-speed<br />

IOL, OL circuits “E6”.<br />

No<br />

�<br />

Reset relay.<br />

Check compressor withstand<br />

resistance.<br />

�<br />

No<br />

Check and modify wiring<br />

Check outdoor interface PC board.<br />

If defective replace board.<br />

�<br />

Is the fixed-speed<br />

IOL circuit normal?<br />

��<br />

Is circuit wiring normal?<br />

�<br />

Yes<br />

Is the fixed-speed<br />

OCR circuit normal?<br />

�<br />

Yes<br />

Yes<br />

57