50<br />

Troubleshooting<br />

Diagnostic procedure for check code<br />

Check code Operation cause<br />

[88] 1. Error connection between <strong>Multi</strong> Controller<br />

Communication alarm between <strong>Multi</strong> Controller and outdoor unit.<br />

and outdoor unit 2. Outdoor PC board error (MCC-1223).<br />

3. <strong>Multi</strong> Controller PC board error (MCC-1210).<br />

4. <strong>Multi</strong> Controller does not recognise outdoor<br />

capacity.<br />

Check lead connection between indoor unit and <strong>Multi</strong> Controller.<br />

If no error is detected, replace <strong>Multi</strong> Controller board (MCC-1210) or outdoor PC board (MCC-1223).<br />

Check code Operation cause<br />

[89] 1. No. of connected indoor units/connected over<br />

Indoor over capacity capacity.<br />

2. Incorrect set-up of indoor unit horse power or<br />

set to 0.<br />

Is No. of connected indoor<br />

units acceptable? (*1)<br />

�<br />

Is set-up of indoor unit<br />

horse power correct? (*2)<br />

�<br />

Yes<br />

Yes<br />

Is total capacity of<br />

connected indoor units<br />

within indoor unit diversity?<br />

1. M/C = 135%<br />

2. 4 M/C = 160%<br />

�<br />

Yes<br />

Check IPDU PC board<br />

No<br />

No<br />

No<br />

�<br />

�<br />

�<br />

Indoor units from another system have been<br />

incorrectly connected.<br />

Modify miswiring/installation.<br />

Modify set-up of horse power.<br />

Keep capacity of connected indoor units<br />

within unit diversity.<br />

(*1)<br />

Number of Maximum No. of Indoor unit diversity Maximum system code Maximum code per<br />

<strong>Multi</strong> Controllers indoor units <strong>Multi</strong> Controller<br />

1 4 135% 27 27<br />

2 8 160% 32 27<br />

3 12 27 (13*)<br />

4 16 13<br />

(*2)<br />

Indoor unit Capacity No connection 10 13 16 20 26 36 46<br />

Code number 0 2 3 4 5 6 8 10<br />

(Example: Model RAV-364UH-PE, capacity = 36)