32<br />

Diagnostic procedure<br />

<strong>Multi</strong> Controller<br />

The combination of the display switch and the four 7-segment LEDs (LD 101-LD 104) indicates the<br />

diagnostic details.<br />

7 segment LED display<br />

Unit B Unit D<br />

Unit A Unit C<br />

Capacity rank switches<br />

MCC - 1223<br />

7-segment LED<br />

LD 102 LD 104<br />

LD 101 LD 103<br />

Display switch<br />

<strong>Multi</strong> Controller control board<br />

Switch<br />

position<br />

Indication LD 101LD 102 LD 103 LD 104<br />

0 Serial - - - Receiving Sending - Sending Receiving Receiving - Receiving Sending - Sending Receiving Sending<br />

signal from to to from from from to to from to<br />

unit B unit B unit A unit A oudoor unit D unit D unit C unit C outdoor<br />

unit unit<br />

1 Fault<br />

codes<br />

[E] - Fault code display (normal [00]). Refer to fault code section for details.<br />

2 Frequency Instructed demand frequency of cooling or heating [00 - 1F].<br />

instructions Refer to the <strong>Multi</strong> Controller display conversion table (1) for display switch position “2”<br />

to the outdoor<br />

unit<br />

3 Oil - - - Oil <strong>Super</strong>heat - <strong>Super</strong>heat Oil - - Oil <strong>Super</strong>heat - <strong>Super</strong>heat Oil -<br />

retrieval, retrieval control control retrieval retrieval control control retrieval<br />

superheat<br />

control<br />

unit B unit B unit A unit A unit D unit D unit C unit C<br />

Defrost Displays [dF] during defrost operation<br />

4 Operation M/C operating Outdoor unit operating mode: Heating [H-], Cooling [-C], Simultaneous Heating [Hc],<br />

mode mode:<br />

Heating [H-],<br />

Cooling [C-]*<br />

Simultaneous Cooling [hC], Stop [--], Defrost [J-]<br />

5 Restart<br />

timer<br />

- - - Normal display [0], Restart timer counting [1]<br />

6 Circuit test [c] [k] Displays unit being tested [A b C d] Indicates faulty unit connection [A b C d]<br />

7 PMV A [P] [A] Displays the degree of PMV opening (0-240) as a hexadecimal code:<br />

8 PMV B [P] [b] [00]: Closed, [FO]: Fully open<br />

9 PMV C [P] [c]<br />

10 PMV D [P] [d]<br />

11 ThA [h] [A] Displays sensor temperature<br />

12 ThB [h] [b] Refer to the <strong>Multi</strong> Controller sensor temperature conversion table (1).<br />

13 ThC [h] [c]<br />

14 ThD [h] [d]<br />

15 ThX [h] [H]<br />

* and Simultaneous Cooling/Heating [HC], Defrost [J-]