18.12.2012 Views

Super Multi System - Toshiba

Super Multi System - Toshiba

Super Multi System - Toshiba

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Troubleshooting<br />

Diagnostic procedure for check code<br />

Check code Operation cause<br />

[b5] 1. External device error.<br />

External input display fault 2. Indoor PC board error.<br />

[b6]<br />

External interlock display fault<br />

Fault on CN17 - fault on external device<br />

(accessory)<br />

Is the external device connected<br />

to connector CN17 ?<br />

�<br />

Is the external device<br />

operating normally ?<br />

�<br />

Yes<br />

Yes<br />

Check cause of the operation.<br />

No<br />

No<br />

�<br />

�<br />

Check indoor PC board.<br />

If defective, replace.<br />

Check external device.<br />

If defective, replace.<br />

Check code Operation cause<br />

[d3] Error of temp. sensor incorporated in IGBT<br />

TH sensor alarm<br />

Refer to outdoor unit<br />

(Inverter Gate Bi-Polar Transistor)<br />

There is an error with the temp. sensor incorporated in IGBT. Check connectors CN07 on IPDU PC board<br />

and CN600 on interface PC board. If there is no problem, replace IPDU PC board.<br />