18.12.2012 Views

Super Multi System - Toshiba

Super Multi System - Toshiba

Super Multi System - Toshiba

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

62<br />

Troubleshooting<br />

Diagnostic procedure for check code<br />

Check code Operation cause<br />

[dA] 1. Power supply failure.<br />

Abnormal overheat of heat sink 2. Outdoor fan error.<br />

Refer to outdoor unit 3. Heat sink installation failure.<br />

4. Blockage of heat sink cooling duct.<br />

5. Defective inverter PC board.<br />

Is power supply voltage normal ?<br />

�<br />

Is the wiring connector<br />

connection normal on the<br />

inverter PC board ?<br />

�<br />

Yes<br />

Yes<br />

Is outdoor fan normal ?<br />

�<br />

Is there a screw loose on the<br />

IGBT module or heat sink on<br />

inverter PC board ?<br />

�<br />

Yes<br />

No<br />

Is there a blockage in the heat<br />

sink cooling duct ?<br />

No<br />

�<br />

Check inverter PC board.<br />

No<br />

No<br />

No<br />

Yes<br />

Yes<br />

�<br />

�<br />

�<br />

�<br />

�<br />

Check power supply.<br />

Check the circuit wiring, for example wiring to the<br />

inverter compressor or connector connection.<br />

Check fan and fan motor.<br />

Tighten screws.<br />

Remove blockage.