62<br />
Troubleshooting<br />
Diagnostic procedure for check code<br />
Check code Operation cause<br />
[dA] 1. Power supply failure.<br />
Abnormal overheat of heat sink 2. Outdoor fan error.<br />
Refer to outdoor unit 3. Heat sink installation failure.<br />
4. Blockage of heat sink cooling duct.<br />
5. Defective inverter PC board.<br />
Is power supply voltage normal ?<br />
�<br />
Is the wiring connector<br />
connection normal on the<br />
inverter PC board ?<br />
�<br />
Yes<br />
Yes<br />
Is outdoor fan normal ?<br />
�<br />
Is there a screw loose on the<br />
IGBT module or heat sink on<br />
inverter PC board ?<br />
�<br />
Yes<br />
No<br />
Is there a blockage in the heat<br />
sink cooling duct ?<br />
No<br />
�<br />
Check inverter PC board.<br />
No<br />
No<br />
No<br />
Yes<br />
Yes<br />
�<br />
�<br />
�<br />
�<br />
�<br />
Check power supply.<br />
Check the circuit wiring, for example wiring to the<br />
inverter compressor or connector connection.<br />
Check fan and fan motor.<br />
Tighten screws.<br />
Remove blockage.