Is drain pump connected?<br />
Does float switch operate?<br />
Does drainage water collect?<br />
Does drain pump operate?<br />
Check for blockage of<br />
drainage hose.<br />
Troubleshooting<br />
Diagnostic procedure for check code<br />
Check code Status of air conditioner Operation cause<br />
[0b] Operation stops for <strong>Multi</strong> 1. Float switch disconnection.<br />
Drain pump fault Controller fault. 2. Drain pump operation error.<br />
Indoor unit or <strong>Multi</strong> Indoor unit fan continues for 3. Drain hose blockage.<br />
Controller unit fault.<br />
�<br />
�<br />
�<br />
�<br />
Yes<br />
Yes<br />
Yes<br />
Yes<br />
No<br />
No<br />
Is circuit wiring<br />
normal?(*1)<br />
(*1) For confirmation, check voltage under condition that<br />
connector is connected to CN10, pins 5 and 7,<br />
PJ10, pins 1 and 2<br />
No<br />
No<br />
�<br />
Is power to drain<br />
pump turned on?(*2)<br />
�<br />
Yes<br />
Drain pump error<br />
Check code<br />
[0C]<br />
Operation cause<br />
Indoor sensor (TA) short or open circuit alarm TA sensor open/short<br />
�<br />
No<br />
No<br />
�<br />
�<br />
�<br />
�<br />
�<br />
Check connection of connector CN10<br />
(Drain pump: Indoor main, PC board<br />
(MCC-1292), CN10)<br />
(Drain pump: <strong>Multi</strong> Controller, PC board<br />
(MCC-1210) PJ10)<br />
Check and modify wiring circuit.<br />
(MCC-1292), (MCC-1210)<br />
Indoor PC board error<br />
(MCC-1292), (MCC-1210)<br />
Float switch error<br />
Check and modify wiring<br />
circuit.<br />
(*2) Check whether voltage of CN10/PJ10, pins<br />
1 and 2/1 to 3 of the indoor main PC board,<br />
is 230V or not (MCC-1292), (MCC-1210).<br />
TA sensor open/short has been detected. Check disconnection of connector connection (TA sensor: CN04)<br />
circuit and resistance value characteristics of sensor.<br />
When the sensors are normal, replace indoor PC board (MCC-1292).<br />
Check code Status of air conditioner Operation cause<br />
[0D] Indoor unit fan stops. TC sensor open/short<br />
Indoor sensor (TC) short ‘Preheat defrost’ is<br />
or open circuit alarm displayed on R/C.<br />
TC sensor open/short has been detected. Check disconnection of connection (TC sensor: CN05) circuit<br />
and resistance value characteristics of sensor.<br />
When the sensors are normal, replace indoor PC board (MCC-1292).