18.12.2012 Views

Super Multi System - Toshiba

Super Multi System - Toshiba

Super Multi System - Toshiba

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

42<br />

Troubleshooting<br />

Diagnostic procedure for check code<br />

Check code Status of air conditioner Operation cause<br />

[14] Operation stops 1. Outdoor unit power supply error.<br />

IPDU short circuit 2. Wiring error on IPDU PC board.<br />

protective operation 3. AC fuse disconnection.<br />

alarm (Power Transistor) 4. Inverter compressor error.<br />

5. Defective IPDU PC board.<br />

Is the power supply voltage<br />

of the outdoor unit normal?<br />

�<br />

Is the connection of the wiring<br />

connector on the IPDU PC board<br />

normal?<br />

�<br />

Is AC 20A fuse working?<br />

�<br />

Is inverter compressor normal?<br />

�<br />

Is smoothing capacitor normal?<br />

(2200µ F,400V x 2)<br />

�<br />

Yes<br />

Yes<br />

Yes<br />

Yes<br />

Yes<br />

Check IPDU PC board.<br />

No<br />

No<br />

No<br />

No<br />

No<br />

�<br />

�<br />

�<br />

�<br />

�<br />

Confirm the power supply line.<br />

Modify connector of wiring.<br />

Replace IPDU PC board and fuse.<br />

Replace IPDU PC board and inverter<br />

compressor.<br />

Confirm capacitance and appearance -<br />

Replace if faulty.<br />

Replace IPDU PC board.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!