Valve and sensor function and operation<br />
<strong>Multi</strong> Controller sensor operation<br />
Sensor and switch operation<br />
Temperature According to a difference between the evaporator outlet temperature and<br />
sensor (ThA, B, C, D) saturation temperature (ThX):<br />
a. Performs superheat control.<br />
(cooling operation)<br />
b. Determines the degree of opening of PMV 2.<br />
(cooling-dominant operation)<br />
Outdoor unit sensor and switch operation<br />
Discharge pressure Determines the frequency of the inverter compressor and the ON/OFF status of<br />
sensor D.O.L. compressor.<br />
Controls the outdoor unit fan operation.<br />
Controls the hot gas bypass SV2.<br />
Controls the changeover from outdoor unit main heat exchanger to sub heat<br />
exchanger.<br />
Suction temperature Controls the degree of opening of PMV 1.<br />
sensor (ThS) Stops operation when ThS > 40°C for 10 minutes (Fault code [A7]).<br />
Discharge temperature Controls the degree of opening of PMV 1.<br />
sensor (ThD1, ThD2) Stops operation when the discharge temperature > 130°C (Fault code [A6]).<br />
Outdoor unit heat Controls the defrost operation.<br />
exchanger sensor (TE) Controls the outdoor unit fan operation.<br />
Heating operation Controls the high pressure release valve SV1.<br />
Outdoor temperature Controls the hot gas bypass SV2.<br />
sensor (ThO) Controls the outdoor unit fan operation.<br />
Prevents heating operation when ThO > 25°C.<br />
High pressure switch Stops operation when Pd > 30 kgf/cm2G. Low pressure switch Stops operation when suction pressure < 0.25 kgf/cm2G: After 30 seconds for cooling operation.<br />
After 10 minutes for heating operaton.<br />
The low pressure switch is ignored during defrost operation.