Troubleshooting<br />

Diagnostic procedure for check code<br />

Check code Operation cause<br />

[A6] 1. Outdoor unit service valve closed.<br />

Discharge temperature TD1 and TD2 alarm 2. Cooling bypass PMV error.<br />

(>130°C) 3. TD sensor error.<br />

4. Insufficient refrigerant, blockage in pipe.<br />

5. Blockage of PMV assembly on the liquid line.<br />

Are the gas pipe and liquid pipe<br />

service valves of the outdoor unit<br />

fully open ?<br />

�<br />

Are PMV 2 and SV13<br />

operating normally?<br />

�<br />

Is the cooling bypass<br />

PMV 1 normal ?<br />

�<br />

Yes<br />

Yes<br />

Are the resistance characteristics<br />

of TD sensor normal ?<br />

�<br />

Yes<br />

Yes<br />

Is wiring correct ?<br />

Yes<br />

�<br />

Insufficient refrigerant, blockage,<br />

pipe breakage.<br />

<strong>Multi</strong> Controller blockage.<br />

No<br />

No<br />

No<br />

No<br />

No<br />

�<br />

�<br />

�<br />

�<br />

�<br />

Open valves fully.<br />

Replace defective part.<br />

Cooling bypass PMV 1 error.<br />

Replace TD sensor.<br />

Correct wiring.<br />

(Check miswiring of the outdoor unit according to miswiring check function.)<br />

55