Control features<br />

Outdoor unit<br />

No. Control Description Diagram<br />

1 Defrost During heating operation, defrost is<br />

(Heating mode) controlled by the outdoor unit heat<br />

exchanger temperature sensor (TE).<br />

When the cumulative operating time with<br />

TE in zone [A] has amounted to 25 minutes,<br />

defrost operation starts. Subsequent<br />

defrosts occur after a cumulative time of 55<br />

minutes. When heating operation resumes<br />

after defrost, the timer is reset.<br />

The maximum defrost period after TE<br />

returns to zone [B] is 1 minute.<br />

Heating operation resumes immediately<br />

after TE returns to zone [C].<br />

2 Oil retrieval During cooling operation, oil retrieval is<br />

(Cooling mode) performed if one or more Indoor units are<br />

OFF.<br />

If this condition is satisfied, when cooling<br />

operation commences, oil retrieval takes<br />

place for 1 minute.<br />

If cooling operation continues, oil retrieval is<br />

repeated for 1 minute every 60 minutes.<br />

During oil retrieval the following occurs:<br />

a. All <strong>Multi</strong> Controller PMVs are opened.<br />

The degree of opening is dependant<br />

on the capacity of the Indoor unit .<br />

b. If the D.O.L. compressor is OFF the<br />

inverter compressor speed increases<br />

to SD.<br />

When cooling operation ends the timer is<br />

reset.<br />

3 <strong>Super</strong>heat control <strong>Super</strong>heat is controlled by the <strong>Multi</strong><br />

(Cooling mode) Controller for cooling operation.<br />

The level of superheat is determined by the<br />

difference between the evaporator outlet<br />

temperature for each indoor unit (ThA, B,<br />

C, D) and the saturation temperature (ThX).<br />

If the superheat of an indoor unit enters<br />

zone [Y], the relevant M/C PMV opens<br />

further to compensate for this increase. The<br />

degree of additional opening is dependant<br />

on the capacity of the indoor unit.<br />

When zone [Z] is reached the PMV opening<br />

is held at the level set in zone [Y].<br />

When the level of superheat returns to zone<br />

[X] the control is cancelled.<br />

Temp.<br />

(°C)<br />

Oil<br />

retrieval<br />

12<br />

8<br />

-3<br />

<strong>Super</strong>heat<br />

(°C)<br />

A<br />

Cooling mode<br />

C<br />

B<br />

60 min. < 60 min.<br />

1 min. 1 min.<br />

13<br />

9<br />

Y<br />

X<br />

Oil<br />

retrieval<br />

Z<br />

Compr.<br />

off<br />

Timer<br />

reset<br />

63