56<br />

Troubleshooting<br />

Diagnostic procedure for check code<br />

Check code Operation cause<br />

[A7] 1. Outdoor unit service valve closed.<br />

Suction temperature (TS) alarm (>40°C) 2. Blockage PMV assembly on the liquid line.<br />

3. TS pressure switch error.<br />

4. Insufficient refrigerant, blockage in pipe.<br />

Are the gas pipe and liquid pipe<br />

service valves of the outdoor unit<br />

fully open ?<br />

�<br />

Is there a blockage in the<br />

expansion valve on the liquid line?<br />

�<br />

Yes<br />

No<br />

Are the characteristics of TS<br />

pressure switch normal?<br />

(N/C type)<br />

Yes<br />

�<br />

Insufficient refrigerant, blockage,<br />

pipe breakage.<br />

No<br />

Yes<br />

No<br />

Check code<br />

[AA]<br />

Operation cause<br />

High pressure sensor (Pd) short circuit Pd sensor output voltage alarm<br />

�<br />

�<br />

�<br />

Open valves fully.<br />

Replace expansion valve.<br />

Replace TS pressure switch.<br />

If there is an abnormal output voltage of Pd sensor: Check connector circuit (Pd sensor: PJ7) and output<br />

voltage of the sensor.<br />

If the sensor is normal, replace the outdoor interface PC board.<br />

Sensor characteristics:<br />

Input 12 V DC (± 10%) across red and black leads of the pressure sensor.<br />

Output 0.5 to 4.5 V at 0 to 2.45 MPa across white and black leads of the pressure sensor.