Valve and sensor function and operation<br />
<strong>Multi</strong> Controller - valve functions<br />
<strong>Multi</strong> Controller<br />
Symbol Name of valve Description of function<br />
PMV (A, B, C, D) Flow rate control valve This opens to the extent corresponding to the capacity<br />
and performance required of each indoor unit.<br />
SVS (A, B, C, D) Suction gas valve Opens when commands from the indoor units require<br />
cooling operation.<br />
SVD (A, B, C, D) Discharge gas valve Opens when commands from the indoor units require<br />
heating operation.<br />
SVSS Pressure reducing Opens when the number of units in heating operation<br />
solenoid valve is reduced (heating to shutdown or cooling).<br />
Opens when defrost operation starts.<br />
Opens during oil retrieval control in cooling operation.<br />
SVDD Pressure increasing Opens when the number of units in heating operation<br />
solenoid valve is increased (shutdown or cooling to heating).<br />
Opens while control is performed to prevent liquid<br />
in discharge pipe from being blocked.<br />
SVH <strong>Super</strong>heat solenoid valve Opens when unit in cooling operation is present.<br />
<strong>Multi</strong> Controller - valve operation<br />
Outdoor operation mode Indoor operation mode SVD SVS PMV<br />
Shutdown Shutdown, fan OFF OFF Fully closed<br />
During operation Shutdown, fan OFF ON Fully closed<br />
Cooling OFF ON Rated opening<br />
Cooling thermo-control (@ setpoint) OFF OFF ON Fully closed<br />
Heating ON OFF Rated opening<br />
Heating thermo-control (@ setpoint) OFF ON OFF Fully closed<br />
65