Planning Guide<br />
Principle of operation<br />
Auto speed control applies to the main (base-load) pump head.<br />
With full stabilisation of this aggregate, i.e. with the nominal pump<br />
speed achieved and the start of the peak load requirement, the peak<br />
load aggregate switches in at a fixed speed (nominal speed), whilst<br />
the power of the controlled base load pump is directly reduced and<br />
adjusted to the load point. Pressure surges resulting from starting<br />
and stopping the trailing pumps are relatively minor and in practice<br />
have no appreciable effect. In parallel operation the constant speed<br />
peak load aggregate and the controllable base load aggregate are<br />
added, based on delivery flow, which in this operating situation readjusts<br />
for the respective peak load requirement.<br />
The switch-point for adding the peak-load head is determined by means<br />
of a unit-integrated electronic assessment logic.<br />
Note:<br />
Peak-load control functions of Wilo auto control systems are only<br />
possible on head- or differential temperature-sensitive control<br />
modes.<br />
Further information on pump regulation is contained in the catalogue<br />
section “Switching devices and control systems”.<br />
Twin-head pump switching<br />
There are two operating modes for the operation of twin-head<br />
pumps:<br />
- Standby switching of one pump with the other is on duty in singlepump<br />
operation.<br />
- Peak load switching with parallel operation of both pumps, which are<br />
also combined from a control option on the respective operating<br />
pump.<br />
Operating modes<br />
Standby operation Peak load operation<br />
No. I or No. II pump in operation Both pumps operating<br />
Duty pump uncontrolled<br />
Pump I<br />
Investment costs:<br />
Operating costs:<br />
Wilo Catalogue A2 - <strong>Glanded</strong> pumps<br />
Pump II<br />
lower<br />
high<br />
Pump I + II<br />
higher<br />
low<br />
Operating pump controlled by means of Wilo control system<br />
Pump I<br />
Investment costs<br />
(Including control):<br />
Operating costs:<br />
Pump II<br />
higher<br />
higher<br />
Pump I + II<br />
lower<br />
low<br />
Operating Functions<br />
Wilo switching devices feature the following operating functions:<br />
A standby switching, fault-sensitive or time-sensitive operational<br />
changeover Pump I Pump II.<br />
B Peak-load operation for load- or time-sensitive automatic load<br />
adjustment through ON / OFF control of the trailing pump.<br />
C Infinitely-variable speed control of the leading pump for load- or<br />
time-sensitive automatic power adjustment when the trailing<br />
pump it switched on for infinitely-variable peak-load service.<br />
Switchgear Switch function<br />
A B C<br />
SD Series (Standby / Cut-in) • • –<br />
S2R 3D (Standby / Cut-in) • • –<br />
CR System (stepless) • • •<br />
Series S2R 3D / SD<br />
Changeover panels for auto-control of operating and standby pumps<br />
of dual sets. Automatic fault-actuated changeover from operating to<br />
standby pump. Automatic time-controlled routine duty changeover<br />
of operating and standby pumps.<br />
Additional peak load switching through series standard connection<br />
option for the 2nd pump.<br />
Short-term parallel running is integrated into the changeover<br />
sequence to avoid the occurrence of valve noise during uncontrolled<br />
changeover.<br />
Version in ISO housing, Protection Class: IP 41. Potential-free contact<br />
for collective fault signal.<br />
Connection options to three-phase current 400 V, 50 Hz, or threephase<br />
230 V, 50 Hz.<br />
Non-standard voltages and frequencies on request.<br />
Technical Data<br />
Switchgear type Motor power<br />
[kW]<br />
S2R 3D 0.37-3<br />
SD 5.5 4-5.5<br />
SD 9 7.5- 9<br />
SD 18.5 11-18.5<br />
SD 30 22-30<br />
SD 37 37<br />
13<br />
Planning Guide<br />
Energy-saving pumps<br />
Standard pumps<br />
Special pumps<br />
Pump management