Planning Guide<br />

Principle of operation<br />

Auto speed control applies to the main (base-load) pump head.<br />

With full stabilisation of this aggregate, i.e. with the nominal pump<br />

speed achieved and the start of the peak load requirement, the peak<br />

load aggregate switches in at a fixed speed (nominal speed), whilst<br />

the power of the controlled base load pump is directly reduced and<br />

adjusted to the load point. Pressure surges resulting from starting<br />

and stopping the trailing pumps are relatively minor and in practice<br />

have no appreciable effect. In parallel operation the constant speed<br />

peak load aggregate and the controllable base load aggregate are<br />

added, based on delivery flow, which in this operating situation readjusts<br />

for the respective peak load requirement.<br />

The switch-point for adding the peak-load head is determined by means<br />

of a unit-integrated electronic assessment logic.<br />

Note:<br />

Peak-load control functions of Wilo auto control systems are only<br />

possible on head- or differential temperature-sensitive control<br />

modes.<br />

Further information on pump regulation is contained in the catalogue<br />

section “Switching devices and control systems”.<br />

Twin-head pump switching<br />

There are two operating modes for the operation of twin-head<br />

pumps:<br />

- Standby switching of one pump with the other is on duty in singlepump<br />

operation.<br />

- Peak load switching with parallel operation of both pumps, which are<br />

also combined from a control option on the respective operating<br />

pump.<br />

Operating modes<br />

Standby operation Peak load operation<br />

No. I or No. II pump in operation Both pumps operating<br />

Duty pump uncontrolled<br />

Pump I<br />

Investment costs:<br />

Operating costs:<br />

Wilo Catalogue A2 - <strong>Glanded</strong> pumps<br />

Pump II<br />

lower<br />

high<br />

Pump I + II<br />

higher<br />

low<br />

Operating pump controlled by means of Wilo control system<br />

Pump I<br />

Investment costs<br />

(Including control):<br />

Operating costs:<br />

Pump II<br />

higher<br />

higher<br />

Pump I + II<br />

lower<br />

low<br />

Operating Functions<br />

Wilo switching devices feature the following operating functions:<br />

A standby switching, fault-sensitive or time-sensitive operational<br />

changeover Pump I Pump II.<br />

B Peak-load operation for load- or time-sensitive automatic load<br />

adjustment through ON / OFF control of the trailing pump.<br />

C Infinitely-variable speed control of the leading pump for load- or<br />

time-sensitive automatic power adjustment when the trailing<br />

pump it switched on for infinitely-variable peak-load service.<br />

Switchgear Switch function<br />

A B C<br />

SD Series (Standby / Cut-in) • • –<br />

S2R 3D (Standby / Cut-in) • • –<br />

CR System (stepless) • • •<br />

Series S2R 3D / SD<br />

Changeover panels for auto-control of operating and standby pumps<br />

of dual sets. Automatic fault-actuated changeover from operating to<br />

standby pump. Automatic time-controlled routine duty changeover<br />

of operating and standby pumps.<br />

Additional peak load switching through series standard connection<br />

option for the 2nd pump.<br />

Short-term parallel running is integrated into the changeover<br />

sequence to avoid the occurrence of valve noise during uncontrolled<br />

changeover.<br />

Version in ISO housing, Protection Class: IP 41. Potential-free contact<br />

for collective fault signal.<br />

Connection options to three-phase current 400 V, 50 Hz, or threephase<br />

230 V, 50 Hz.<br />

Non-standard voltages and frequencies on request.<br />

Technical Data<br />

Switchgear type Motor power<br />

[kW]<br />

S2R 3D 0.37-3<br />

SD 5.5 4-5.5<br />

SD 9 7.5- 9<br />

SD 18.5 11-18.5<br />

SD 30 22-30<br />

SD 37 37<br />

13<br />

Planning Guide<br />

Energy-saving pumps<br />

Standard pumps<br />

Special pumps<br />

Pump management