Pump Management Systems Wilo-Control<br />

Pump Control<br />

Series description Wilo-IR-Monitor<br />

Series Main menu<br />

descrip- The main menu of the IR-Monitor is divided into 6 function menus:<br />

tion Wilo-<br />

IR-Monitor Menu 1: “Communication”<br />

This menu initiates the automatic linkup between<br />

the IR-Monitor and the pump.<br />

Selective activation of individual pumps within a set<br />

of pumps 1000 is also possible here.<br />

Menu 2: “Display”<br />

Here it is possible to read system data, e.g. actual<br />

electrical and hydraulic values, operating status,<br />

operating mode, fault reports.<br />

For correct interpretation, the display always distinguishes<br />

clearly between “Single-” and “Twin-head<br />

pump”.<br />

Menu 3: “Operate”<br />

In this menu, data can be both displayed (current<br />

setpoint value) and changed, e.g. control mode,<br />

setpoint value, pump ON / OFF, disabling the manual<br />

operating level at the pump (pump ON / OFF,<br />

Ext. Aus and SSM remaining active).<br />

Menu 4: “Statistics”<br />

So that operating periods can be analysed, this<br />

menu offers clearly definable histograms of hydraulic<br />

performance (volumetric flow Q), thus giving an<br />

appreciation of the system load conditions over<br />

a definable operating period. It also records hoursrun<br />

and operating data.<br />

Menu 5: “Service”<br />

In the service menu the user is given the open of<br />

fault diagnosis, fault statistics, function-testing the<br />

pump, the IR-Monitor and the serial digital interface,<br />

as well as direction-of-rotation check and<br />

frequency measurement of the rotating field.<br />

The latter two checks can also be conducted with<br />

all conventional pumps without IR interface.<br />

Menu 6: “Adjust”<br />

Language selection, contrast and time-out settings,<br />

changing and activating the personal password<br />

are available to adapt the IR-Monitor to suit<br />

individual requirements.<br />

206 Subject to change without prior notice 09/2006 WILO AG