Switching and Control Devices<br />

Wilo-VR, CRn, and CR control devices<br />

Control modes<br />

Differential pressure – delivery-superimposed (p-q)<br />

Delivery head H [%]<br />

Power requirement P [%]<br />

Fig.: The pump curve behaviour of a multi-pump system with stepless delivery-superimposed differential<br />

pressure control (p-q)<br />

Wilo Catalogue A2 - <strong>Glanded</strong> pumps<br />

Flow volume Q [%]<br />

Δp = constant<br />

Δp = deliverysuperimposed<br />

Key:<br />

Pu H = main pump<br />

Pu S = peak load pump<br />

Q V = full-load flow volume<br />

Q T = part-load capacity<br />

P 1V = full-load power<br />

consumption<br />

P 1T = part-load power<br />

consumption<br />

In order to avoid the time and expenditure<br />

associated with index-circuit evaluation<br />

(extensive and expensive cable routing,<br />

amplifiers, etc.), it is possible to superimpose<br />

the setpoint differential-pressure<br />

value directly with a signal proportional to<br />

delivery. Using this method, it is possible<br />

even with multi-pump systems to achieve a<br />

control-range extension in spite of central<br />

measured-value acquisition (differential<br />

pressure sensor at the pump).<br />

This method requires, in addition to the differential<br />

pressure sensor which is to be fitted<br />

directly on the pump system, the heating-circuit<br />

output or the input of the<br />

consumer rail, the onsite provision by the<br />

customer of a volumetric-flow transmitter<br />

(0 / 4– 20 mA) to be installed in the system's<br />

main feed pipe.<br />

The use of p-q-control is recommended<br />

for such systems whose index circuit or system<br />

performance are not known or in such<br />

cases where long signal distances cannot be<br />

bridged, particularly for such systems where<br />

flow volumetric-flow transmitters are<br />

already available.<br />

>Required accessory:<br />

- DDG differential-pressure sensor<br />

- Volumetric-flow transmitter (onsite)<br />

177<br />

Planning Guide<br />

Energy-saving pumps<br />

Standard pumps<br />

Special In-line <strong>Pumps</strong><br />

Switching and Control Devices<br />