Switching and Control Devices<br />
Wilo-VR, CRn, and CR control devices<br />
Control modes<br />
Differential pressure – delivery-superimposed (p-q)<br />
Delivery head H [%]<br />
Power requirement P [%]<br />
Fig.: The pump curve behaviour of a multi-pump system with stepless delivery-superimposed differential<br />
pressure control (p-q)<br />
Wilo Catalogue A2 - <strong>Glanded</strong> pumps<br />
Flow volume Q [%]<br />
Δp = constant<br />
Δp = deliverysuperimposed<br />
Key:<br />
Pu H = main pump<br />
Pu S = peak load pump<br />
Q V = full-load flow volume<br />
Q T = part-load capacity<br />
P 1V = full-load power<br />
consumption<br />
P 1T = part-load power<br />
consumption<br />
In order to avoid the time and expenditure<br />
associated with index-circuit evaluation<br />
(extensive and expensive cable routing,<br />
amplifiers, etc.), it is possible to superimpose<br />
the setpoint differential-pressure<br />
value directly with a signal proportional to<br />
delivery. Using this method, it is possible<br />
even with multi-pump systems to achieve a<br />
control-range extension in spite of central<br />
measured-value acquisition (differential<br />
pressure sensor at the pump).<br />
This method requires, in addition to the differential<br />
pressure sensor which is to be fitted<br />
directly on the pump system, the heating-circuit<br />
output or the input of the<br />
consumer rail, the onsite provision by the<br />
customer of a volumetric-flow transmitter<br />
(0 / 4– 20 mA) to be installed in the system's<br />
main feed pipe.<br />
The use of p-q-control is recommended<br />
for such systems whose index circuit or system<br />
performance are not known or in such<br />
cases where long signal distances cannot be<br />
bridged, particularly for such systems where<br />
flow volumetric-flow transmitters are<br />
already available.<br />
>Required accessory:<br />
- DDG differential-pressure sensor<br />
- Volumetric-flow transmitter (onsite)<br />
177<br />
Planning Guide<br />
Energy-saving pumps<br />