Switching and Control Devices<br />
Wilo-VR, CRn, and CR control devices<br />
Control modes<br />
Index circuit evaluation<br />
Power cable min. 5 x ... mm2<br />
cross-section according to local regulations<br />
Fig.: Block diagram for impulse-selector operation<br />
Wilo Catalogue A2 - <strong>Glanded</strong> pumps<br />
Motor cable, shielded 7 x 1,5 mm2<br />
Cable, shielded<br />
2 x 1,5 mm2<br />
*** Power cable min. 3 x 1,5 mm2<br />
*** Sensor cable, shielded 3 x 1,5 mm2<br />
*** Impulse selector cable, shielded 2 x 1,5 mm2<br />
All cables onsite<br />
Fixing sundries and cable onsite<br />
Power cable min. 3 x 1,5 mm2<br />
DDG impulse selector<br />
DDG transformer<br />
DDG<br />
DDG<br />
DDG<br />
DDG<br />
It is generally recommended to pick off the<br />
differential-pressure directly at the pump<br />
and to maintain it there at a constant level.<br />
An alternative would be to install the signal<br />
transmitter in the heating system as a<br />
remote signal transmitter in the so-called<br />
index circuit of the system (control-range<br />
extension). Operation with a remote signal<br />
transmitter will partly allow much larger<br />
speed reductions and thus pump performance<br />
reductions. It is essential in this<br />
respect that the selected measuring point<br />
be valid for the consumption performance<br />
of all the system sections.<br />
Where this calculated measuring point in<br />
the index circuit may be subject to shifting<br />
to other parts of the pipe system, optimisation<br />
by means of the Wilo DDG impulse<br />
selector is preferable. Measuring points<br />
ranging from 2 to 4 can be compared on a<br />
continuous basis. Only the lowest measured<br />
value forms the basis for the setpoint /<br />
actual value comparison by the CR controller.<br />
>Required accessory:<br />
- DDG differential-pressure sensor<br />
- Power supply unit DDG (for each DDG)<br />
- Impulse selector DDG (2...4 DDG)<br />
175<br />
Planning Guide<br />
Energy-saving pumps<br />
Standard pumps<br />
Special In-line <strong>Pumps</strong><br />
Switching and Control Devices<br />
Pump Management Systems