Switching and Control Devices<br />

Wilo-VR, CRn, and CR control devices<br />

Control modes<br />

Index circuit evaluation<br />

Power cable min. 5 x ... mm2<br />

cross-section according to local regulations<br />

Fig.: Block diagram for impulse-selector operation<br />

Wilo Catalogue A2 - <strong>Glanded</strong> pumps<br />

Motor cable, shielded 7 x 1,5 mm2<br />

Cable, shielded<br />

2 x 1,5 mm2<br />

*** Power cable min. 3 x 1,5 mm2<br />

*** Sensor cable, shielded 3 x 1,5 mm2<br />

*** Impulse selector cable, shielded 2 x 1,5 mm2<br />

All cables onsite<br />

Fixing sundries and cable onsite<br />

Power cable min. 3 x 1,5 mm2<br />

DDG impulse selector<br />

DDG transformer<br />

DDG<br />

DDG<br />

DDG<br />

DDG<br />

It is generally recommended to pick off the<br />

differential-pressure directly at the pump<br />

and to maintain it there at a constant level.<br />

An alternative would be to install the signal<br />

transmitter in the heating system as a<br />

remote signal transmitter in the so-called<br />

index circuit of the system (control-range<br />

extension). Operation with a remote signal<br />

transmitter will partly allow much larger<br />

speed reductions and thus pump performance<br />

reductions. It is essential in this<br />

respect that the selected measuring point<br />

be valid for the consumption performance<br />

of all the system sections.<br />

Where this calculated measuring point in<br />

the index circuit may be subject to shifting<br />

to other parts of the pipe system, optimisation<br />

by means of the Wilo DDG impulse<br />

selector is preferable. Measuring points<br />

ranging from 2 to 4 can be compared on a<br />

continuous basis. Only the lowest measured<br />

value forms the basis for the setpoint /<br />

actual value comparison by the CR controller.<br />

>Required accessory:<br />

- DDG differential-pressure sensor<br />

- Power supply unit DDG (for each DDG)<br />

- Impulse selector DDG (2...4 DDG)<br />

175<br />

Planning Guide<br />

Energy-saving pumps<br />

Standard pumps<br />

Special In-line <strong>Pumps</strong><br />

Switching and Control Devices<br />

Pump Management Systems