Switching and Control Devices<br />

Wilo-VR, CRn, and CR control devices<br />

Control modes<br />

Temperature control (±T)<br />

Return temperature –T [C]<br />

H [%]<br />

Delivery head<br />

Power consumption P 1 [%]<br />

Control range, adjustable<br />

from 5°C to 50°C,<br />

e.g. 30°C<br />

Max. boundary<br />

min. n = 60 %<br />

min. n = 60 %<br />

Fig.: System diagram of stepless temperature control<br />

Wilo Catalogue A2 - <strong>Glanded</strong> pumps<br />

Outside temperature TA [C]<br />

max. n = 100 %<br />

Control range<br />

Heating curves, basic temperature<br />

Flow volume Q [%]<br />

max. n = 100 %<br />

Energy savings<br />

Flow volume Q [%]<br />

Min. boundary<br />

Feed temperature + T [C]<br />

Pump<br />

performance<br />

diagram Q/H<br />

Pump<br />

performance<br />

diagram Q/P<br />

In the case of pump control as a function of<br />

temperature, the control signal (±T) brings<br />

about a variation of pump performance, but<br />

there is no adaptation by way of feedback<br />

and setpoint / actual value comparison of<br />

the variation or its results.<br />

Fixed motor speeds have been allotted to<br />

the pump for certain feed / return temperatures<br />

in accordance with an empirically predetermined<br />

pump curve.<br />

A decreasing feed temperature (+T) or a rising<br />

return temperature (-T) will result in a<br />

speed reduction and thus in decreasing<br />

pump performance input.<br />

Temperature control ±T can only be<br />

applied to single pump operation. Feed or<br />

return temperature-sensitive peak-load<br />

operation is technically not feasible.<br />

>Required accessory:<br />

- KTY 10 temperature board<br />

or<br />

- PT 100 temperature board<br />

- Temperature sensor TSG or PT 100 (onsite)<br />

179<br />

Planning Guide<br />

Energy-saving pumps<br />

Standard pumps<br />

Special In-line <strong>Pumps</strong><br />

Switching and Control Devices<br />

Pump Management Systems