Switching and Control Devices<br />
Control devices<br />
Series overview<br />
Series: Wilo-VR-HVAC-System<br />
Series: Wilo-CRn-System<br />
Series: Wilo-CR-System<br />
>Control device for glandless and glanded pumps<br />
(electronically regulated stepless pumps and / or pumps with integrated frequency converter)<br />
• Variable-control system for stepless performance control of pumps of the series TOP-E / -ED,<br />
Stratos-D / -Z / -ZD, IP-E / DP-E, IL-E / DL-E, IL-E…BF<br />
• For control modes p-c and p-v in heating / air-conditioning technology and pressure<br />
boosting<br />
• Pump performance splitting with up to 4 units<br />
• Nominal power up to P 2 =22 kW<br />
• Speed range between 100 % and 40 %<br />
• including full motor protection apparatus<br />
>Control device for glandless and glanded pumps<br />
(electronically regulated stepless pumps and / or pumps with integrated frequency converter)<br />
• Comfort-control device for stepless performance control of pumps of the series TOP-E / -ED,<br />
Stratos-D / -Z / -ZD, IP-E / DP-E, IL-E / DL-E, IL-E...BF<br />
• Suitable for all control modes used in heating, air-conditioning and pressure boosting<br />
• Pump performance splitting with up to 6 units<br />
• Nominal power to P 2 = 30 kW (to P 2 = 200 kW on request)<br />
• Speed range between 100 % and 40 %<br />
>Control device for glandless and glanded pumps<br />
(Standard pumps with fixed speeds)<br />
• Comfort-control system for stepless performance control of commercially available circulating<br />
pumps with a three-phase AC motor<br />
• Suitable for all control modes used in heating, air-conditioning and pressure boosting<br />
• Pump performance splitting with up to 6 units<br />
• Nominal power to P 2 = 30 kW (to P 2 = 200 kW on request)<br />
• Speed range between 100 % and 40 %<br />
• including full motor protection apparatus<br />
168 Subject to change without prior notice 09/2006 WILO AG