Switching and Control Devices<br />

Wilo-VR, CRn and CR control devices<br />

Signal Transmitters and Accessories<br />

Signal board 1 – 2<br />

Pump 1 Pump 2 Transformer WM Analog<br />

OUT<br />

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16<br />

Operating<br />

disturbance<br />

Operating<br />

disburbance<br />

Terminal diagram, signal board 1 – 2<br />

Signal board 3 – 6<br />

Operating<br />

Pump 1 Pump 2 FU<br />

disturbance<br />

Pump 3 Pump 4 Pump 5 Pump 6<br />

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16<br />

Operating<br />

disturbance<br />

Operating<br />

disturbance<br />

Operating<br />

disturbance<br />

Operating<br />

disturbance<br />

Pump 3 Pump 4 Pump 5 Pump 6<br />

Terminal diagram, signal board 3 – 6<br />

Low water<br />

+ -<br />

DDG or<br />

speed<br />

Additional board for upgrading Wilo-CR-<br />

System switchgear series for individual run /<br />

single fault signals for single and twin-head<br />

pump systems.<br />

>Function<br />

- Potential-free signal contacts for operation<br />

(NO contact) and fault (NC contact) of:<br />

pump 1, pump 2, frequency converter<br />

- Signalling the digital inputs DIG2 or DIG3,<br />

e.g. frost (heating) or low water (pressure<br />

boosting)<br />

- Analogue output for actual speed value or<br />

actual-value transmitter (can be preselected)<br />

Fixing sundries and CAN-bus cable are<br />

included in the scope of delivery.<br />

Additional board for upgrading Wilo-CR-<br />

System series switchgears for individual<br />

run / single fault signals for three- to sixpump<br />

systems (signalling board 1 – 2 also<br />

required).<br />

>Function<br />

- Potential-free signalling contacts for operation<br />

- (normally open contact) and malfunction<br />

(normally closed contact) of:<br />

pump 3, pump 4, pump 5, pump 6<br />

Fixing sundries and CAN-bus cable are<br />

included in the scope of delivery.<br />

>Technical Data<br />

Analog output: Actual value<br />

Measuring range: 0 – 10 V,<br />

0/4 – 20 mA<br />

(rotational speed or<br />

transmitter)<br />

Input resistance: 10 k or 50 <br />

Resolution: 10 bits<br />

Accuracy: 0.2% of upper limit<br />

+ transmitter<br />

tolerance<br />

Signalling contacts:<br />

Switching capacity: maximum<br />

250 VAC / 2 A<br />

minimum<br />

12 VDC / 10 mA<br />

Maximum cable length:100 m<br />

Terminal<br />

cross-sections: 1.5 mm 2<br />

Ambient temp.: 0°C up to +40°C<br />

Dimensions: 120 mm x 120 mm<br />

Weight: approximately 0.5 kg<br />

>Technical Data<br />

Signalling contacts:<br />

Switching capacity: maximum<br />

250 VAC / 2 A<br />

minimum<br />

12 VDC / 10 mA<br />

Terminal<br />

cross-sections: 1.5 mm 2<br />

Ambient temp.: 0°C up to +40°C<br />

Dimensions: 120 mm x 120 mm<br />

Weight: approximately 0.5 kg<br />

198 Subject to change without prior notice 09/2006 WILO AG