Switching and Control Devices<br />
Wilo-VR, CRn, and CR control devices<br />
Performance features<br />
Control and signalling functions<br />
Remote speed adjustment<br />
(control input)<br />
Remote setpoint adjustment<br />
–<br />
–<br />
0/2- 10 V<br />
0/4- 20 mA<br />
0/2- 10 V<br />
0/4- 20 mA<br />
0 / 2- 10 V<br />
0/4- 20 mA<br />
0/2- 10 V<br />
0/4- 20 mA<br />
Run and fault signal lights • • •<br />
Control input<br />
“Setpoint switchover”<br />
– • •<br />
Control input “Overriding Off” • • •<br />
SBM • • •<br />
SSM • • •<br />
Fault-actuated switchover from<br />
frequency converter to mains<br />
operation<br />
Fault-actuated switchover from<br />
main to standby pump<br />
Status display for pumps and<br />
frequency converters<br />
Equipment features<br />
– – •<br />
• • •<br />
– • •<br />
Motor Protection integrated in pump WSK / SSM, integrated in pump ETA / PTC / WSK<br />
Graphics display Menu navigation / Symbol display Menu navigation / Text display Menu navigation / Text display<br />
User-oriented menu guide with<br />
multi-lingual text display<br />
– • •<br />
Manual Operation Manual / 0 / Auto Manual / 0 / Auto Manual / 0 / Auto<br />
Fault memory 9 messages 35 messages 35 messages<br />
Fault-actuated switchover • • •<br />
Pump kick • • •<br />
Run-time optimisation / Pump<br />
alteration<br />
only time-sensitive pump duty<br />
cycling<br />
• •<br />
Proprietary BUS – – –<br />
RS 485<br />
prepared –<br />
for parameterisation of the<br />
frequency converter<br />
Pump duty splitting up to 4 pumps up to 6 pumps up to 6 pumps<br />
PID controller • • •<br />
Integrated real-time clock with<br />
summer / wintertime switchover<br />
Integrated individual / common<br />
operating hours counter<br />
Run-time optimisation on multipump<br />
systems<br />
Conductivity tests of the actual<br />
value control circuit<br />
• = available, – = not available<br />
Wilo Control Device…<br />
VR-HVAC CRn CR<br />
– • •<br />
• • •<br />
– • •<br />
• • •<br />
172 Subject to change without prior notice 09/2006 WILO AG