Glanded Pumps - THERMO-ECO-ENGINEERING úvod
Glanded Pumps - THERMO-ECO-ENGINEERING úvod
Glanded Pumps - THERMO-ECO-ENGINEERING úvod
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Energy-saving pumps<br />
Twin-head pumps In-line<br />
Terminal diagram, motor data Wilo-VeroTwin-DP-E<br />
Energy-saving pumps Twin-head pumps In-line Terminal diagram, motor data Wilo-VeroTwin-DP-E<br />
Terminal diagram<br />
L1 L2 L3 PE aux Ext. Off L H IN2 GND IN1 GND +24V<br />
MP<br />
1 2<br />
DDS<br />
3<br />
SBM<br />
Motor data<br />
SSM<br />
OFF ON<br />
Maximum loading of contacts for collective run and fault signal: min. 12 V<br />
DC / 10 mA, max. 250 V AC / 1 A.<br />
L1, L2, L3, PE: Mains connection 3 ~ 400 V / 50 Hz<br />
SSM: Potential-free collective fault signal<br />
(changeover contact in accordance with VDI 3814)<br />
SBM: Potential-free collective run signal<br />
(changeover contact in accordance with VDI 3814)<br />
Off Control input “Overriding OFF” (24 V)<br />
MP Interface for the connection of a slave pump for fullyintegrated<br />
twin-head pump management<br />
3 +24 V (output)<br />
2 Earth ()<br />
1 0 – 10 V (input)<br />
corresponds to 40 % – 100 % of the rated motor speed<br />
aux without function<br />
Switchover key activated / deactivated.<br />
Option: IF-Modul (PLR / LON)<br />
Wilo-VeroTwin-DP-E ... Nominal power Rotational speed Power consumption Current<br />
P 2 n P 1max I max<br />
[kW] [rpm] [W] [A]<br />
32 / 160-1.1 / 2 1.1 1100 – 2900 1535 3.5<br />
40 / 115-0.55 / 2 0.55 1100 – 2900 865 1.8<br />
40 / 150-3 / 2 3.0 1100 – 2900 3900 8.4<br />
40 / 160-4 / 2 4.0 1200 – 2900 4540 9.5<br />
50 / 115-0.75 / 2 0.75 1200 – 2900 1150 2.4<br />
50 / 140-3 / 2 3.0 1100 – 2890 4030 8.5<br />
50 / 150-4 / 2 4.0 1100 – 2900 5450 11.0<br />
65 / 115-1.5 / 2 1.5 1100 – 2900 2100 4.7<br />
65 / 130-3 / 2 3.0 1200 – 2900 4000 8.7<br />
65 / 140-4 / 2 4.0 1200 – 2890 4950 10.2<br />
80 / 115-2.2 / 2 2.2 1200 – 2900 2900 6.7<br />
80 / 130-3 / 2 3.0 1200 – 2890 3880 8.4<br />
80 / 140-4 / 2 4.0 1100 – 2900 5300 10.6<br />
Three-phase motor (DM), 2-pole – 3 ~ 400 V, 50 Hz / 3 ~ 380 V, 60 Hz<br />
58 Subject to change without prior notice 09/2006 WILO AG